part
3
O
PERATION
:
C
ONFIGURATION
M
ODE
46
Output 1
cont.
Display
Action
Response
ANTI INTEGRAL SUBMENU:
Press ENTER
25) Display flashes
"
enbl
"
or
"
dsbl
"
.
Press MAX
26) Scroll through the available selections:
Enable
or
Disable
.
If
"
Enabled
"
, this feature allows the error term outside the proportional band to be
calculated and accumulated for integration. This may be an important feature in
applications where fast response time is desirable.
Press ENTER
27) Display flashes
"
stored
"
message and advances to
"
Proportional Band
"
submenu if
Auto PID was disabled, otherwise it will go to
"
Start PID
"
.
START AUTO TUNE PID:
Press ENTER
28) Display flashes
"
enbl
"
or
"
dsbl
"
.
Press MAX
29) Scroll through the available selections:
Enable
or
Disable
.
If
"
Enabled
"
, the controller is ready to calculate P, PI or PID parameters. The
setpoints must be at least 20¡F or 11¡C above the (PV) Process Value in order to
perform autotune, otherwise an error message will be displayed.
Press ENTER
30) Display flashes
"
strd
"
message and advances to the ÒCycle TimeÓ submenu.
To start Auto Tune PlD select PID, enable Auto PID and enable Start PID. Sometimes Auto PID parameter needs fine tuning i.e.
for each 5¡F over shoot increase the Proportional Band (PB) by 15% and for each ±1¡F fluctuation at the Setpoint (SP) increase
reset by 20%.
Once started, display shows Ò
A.tun
Ó with the letters blinking in the rotating pattern. Do not perform any
operations or settings before first stopping Auto Tune. Any alarms or other output is disabled during Auto Tune.
STRT
ENBL
STRT
PID
ANTI
ENBL
ANTI
I NTG
Note
☞
Summary of Contents for MICROMEGA CN77000 series
Page 4: ...NOTES ...
Page 19: ...SETUP part 2 11 Dip Switch Settings ...
Page 31: ...Figure 3 2 Flowchart for Input Type OPERATION CONFIGURATION MODE part 3 23 ...
Page 36: ...Figure 3 3 Flowchart for Reading Configuration part 3 OPERATION CONFIGURATION MODE 28 ...
Page 45: ...Figure 3 5 Flowchart for Loop Break OPERATION CONFIGURATION MODE part 3 37 ...
Page 49: ...OPERATION CONFIGURATION MODE part 3 41 Figure 3 6 Flowchart for Output 1 ...
Page 59: ...OPERATION CONFIGURATION MODE part 3 51 Figure 3 7 Flowchart for Output 2 ...
Page 65: ...OPERATION CONFIGURATION MODE part 3 57 Figure 3 8 Flowchart for Ramp Soak ...