![background image](http://html1.mh-extra.com/html/omega/micromega-cn77000-series/micromega-cn77000-series_user-manual_4057365071.webp)
O
PERATION
:
C
ONFIGURATION
M
ODE
part
3
63
Analog Output Option
cont.
Display
Action
Response
READING 1
Press ENTER
6) Display flashes 1st digit of previous ÒReading 1Ó value.
Press MAX & MIN
7) Enter "Reading 1" value.
Press ENTER
8) Display advances to
"
o
Ut1
"
.
OUT 1
Press ENTER
9) Display flashes 1st digit of previous ÒOut 1Ó value.
Press MAX & MIN
10) Enter "Out 1" value.
Press ENTER
11) Display advances to "Reading 2".
READING 2
Press ENTER
12) Display flashes 1st digit of previous ÒReading 2Ó value.
Press MAX & MIN
13) Enter "Reading 2" value.
Press ENTER
14) Display advances to
"
o
ut.2
"
.
OUT 2
Press ENTER
15) Display flashes 1st digit of previous ÒOut 2Ó value.
Press MAX & MIN
16) Enter "Out 2" value.
Press ENTER
17) Display advances to the "Communication Option" menu.
The above example is for 0-10 of the entire range of the process input and analog
output. For 0-20 mA output all you need is to set ÒOut 2Ó to
20.00
.
o
UT.2
10.00
RD 2
9999
o
UT.1
00.00
RD 1
0000
Note
☞
Summary of Contents for MICROMEGA CN77000 series
Page 4: ...NOTES ...
Page 19: ...SETUP part 2 11 Dip Switch Settings ...
Page 31: ...Figure 3 2 Flowchart for Input Type OPERATION CONFIGURATION MODE part 3 23 ...
Page 36: ...Figure 3 3 Flowchart for Reading Configuration part 3 OPERATION CONFIGURATION MODE 28 ...
Page 45: ...Figure 3 5 Flowchart for Loop Break OPERATION CONFIGURATION MODE part 3 37 ...
Page 49: ...OPERATION CONFIGURATION MODE part 3 41 Figure 3 6 Flowchart for Output 1 ...
Page 59: ...OPERATION CONFIGURATION MODE part 3 51 Figure 3 7 Flowchart for Output 2 ...
Page 65: ...OPERATION CONFIGURATION MODE part 3 57 Figure 3 8 Flowchart for Ramp Soak ...