Reading Scale
Scale = (UD - LD)/(UI -LI), where: UD - Upper Display, LD - Low Display
UI - Upper Input, LI - Low Input
Scale = (100 - 0)/(9999-2000) = 0.0125016 (These values were obtained from example on previous Section 3: Reading Configuration
with Process)
0.0125016 = 125016 x 10^ -7, where 125016 is Reading Scale Data, Decimal Point = 7
RDGSC.23~20 = 8 (DP = 7); RDGSC.19 = 0 (direct scale); RDGSC. 18 ~0 = 1E858Hex (125016 Dec)
Binary Code:
Send command: *W1481E858 (scale = 81E858)