part
3
O
PERATION
:
C
ONFIGURATION
M
ODE
Output 1
cont.
Display
Action
Response
CYCLE TIME SUBMENU:
Press ENTER
37) Display flashes 1st digit of the previous
"
Cycle Time
"
value.
Press MAX & MIN
38) Press MAX and MIN buttons to enter a new
"
Cycle Time
"
value. (1 to 199 seconds).
Press ENTER
39) Display flashes
"
stored
"
message and advances to
"
Damping Factor
"
submenu.
A Cycle Time selected between 1 and 199 seconds determines the total On/Off time of each proportional cycle. For example,
a 15 second Cycle Time means that every 15 seconds the output will turn on for part or all of the cycle. For Relay control
outputs, do not select a cycle time of less than 7 seconds or the relays life time will be shortened. For a Cycle Time of less
than 7 seconds select SSR or DC pulse. Use an external SSR with the DC pulse option for higher currents (higher than 1 Amp).
CYCL
0010
CYCL
TIME
Note
☞
48
Summary of Contents for MICROMEGA CN77000 series
Page 4: ...NOTES ...
Page 19: ...SETUP part 2 11 Dip Switch Settings ...
Page 31: ...Figure 3 2 Flowchart for Input Type OPERATION CONFIGURATION MODE part 3 23 ...
Page 36: ...Figure 3 3 Flowchart for Reading Configuration part 3 OPERATION CONFIGURATION MODE 28 ...
Page 45: ...Figure 3 5 Flowchart for Loop Break OPERATION CONFIGURATION MODE part 3 37 ...
Page 49: ...OPERATION CONFIGURATION MODE part 3 41 Figure 3 6 Flowchart for Output 1 ...
Page 59: ...OPERATION CONFIGURATION MODE part 3 51 Figure 3 7 Flowchart for Output 2 ...
Page 65: ...OPERATION CONFIGURATION MODE part 3 57 Figure 3 8 Flowchart for Ramp Soak ...