Command Formats
cont.
OUT2CNFG.0
= 0 On/off
OUT2CNFG.1
= 0 Reverse
OUT2CNFG.2
= 0 Manual PID
1 PID
1 Direct
1 Auto PID
OUT2CNFG.3
= 0 Ramp Disable
OUT2CNFG.4
= 0 Soak Disable
OUT2CNFG.765
= 000 Damping 1
1 Ramp Enable
1 Soak Enable
001 Damping 2
010 Damping 3
011 Damping 4
100 Damping 5
101 Damping 6
110 Damping 7
111 Damping 8
Example:
Set On/Off, Reverse, Auto PID Disable, Ramp, Disable, Soak Disable, Damping 5. The command data is
10000000Bin = 80Hex. Send *W0D85.