![background image](http://html1.mh-extra.com/html/omega/micromega-cn77000-series/micromega-cn77000-series_user-manual_4057365038.webp)
part
3
O
PERATION
:
C
ONFIGURATION
M
ODE
30
Reading Configuration
cont.
Display
Action
Response
FILTER CONSTANT SUBMENU:
Press ENTER
9) Display flashes previous selection for filter constant.
Press MAX
10) Scroll though the available selections:
0001, 0002, 0004, 0008, 0016, 0032,
0064, 0128. - Default is 0004
Press ENTER
11)
Display flashes
"
stored
"
message only if change was made.
For PID control select filter value 0001-0004. A filter value of 2 is approximately equal
to 1 sec. RC low pass time constant.
If Process was selected in the
"
Input Type
"
menu the display will advance to
"
Input SC & OFF
"
, otherwise the display advances to the
"
Alarm 1
"
menu.
The
Filter Constant
submenu allows the user to specify the number of readings stored in the digital averaging filter.
FLTR
0001
fltr
Cnst
Note
☞
Note
☞
Summary of Contents for MICROMEGA CN77000 series
Page 4: ...NOTES ...
Page 19: ...SETUP part 2 11 Dip Switch Settings ...
Page 31: ...Figure 3 2 Flowchart for Input Type OPERATION CONFIGURATION MODE part 3 23 ...
Page 36: ...Figure 3 3 Flowchart for Reading Configuration part 3 OPERATION CONFIGURATION MODE 28 ...
Page 45: ...Figure 3 5 Flowchart for Loop Break OPERATION CONFIGURATION MODE part 3 37 ...
Page 49: ...OPERATION CONFIGURATION MODE part 3 41 Figure 3 6 Flowchart for Output 1 ...
Page 59: ...OPERATION CONFIGURATION MODE part 3 51 Figure 3 7 Flowchart for Output 2 ...
Page 65: ...OPERATION CONFIGURATION MODE part 3 57 Figure 3 8 Flowchart for Ramp Soak ...