45
Output 1
cont.
Display
Action
Response
AUTO PID SUBMENU:
Press ENTER
19) Display flashes
"
enbl
"
or
"
dsbl
"
.
Press MAX
20) Scroll through the available selections: Enable or Disable.
If
"
Enabled
"
, the controller can determine, by enabling Start PID, the optimum values
for the three adjustments Ñ Proportional, Reset and Rate corresponding to P, I, and
D. These values may be changed once the auto tuning is complete. If
"
Disabled
"
is
selected, the user will manually enter these three adjustment values. If you want the
controller to do the auto
PID
and the
P
,
PI
or
PID
, first select auto disable and enter
0000 for the unwanted parameter. e.g. for
PI
enter 0000 for the rate.
Press ENTER
21) Display flashes
"
stored
"
message and advances to
"
Adaptive Control
"
submenu.
*ADAPTIVE CONTROL SUBMENU:
*
(NOT INSTALLED)
Press ENTER
22) Display flashes
"
enbl
"
or
"
dsbl
"
.
Press MAX
23) Scroll through the available selections:
Enable
or
Disable
.
If
"
Enabled
"
, the Adaptive Tuning dynamically changes and updates the P, I, and D
parameters for optimum control. The adaptive tuning is useful when the load
continuously changes thereby requiring new values for
P
,
I
,
and
D
.
Press ENTER
24) Display flashes
"
stored
"
message and advances to
"
Anti Integral
"
submenu.
ADPT
ENBL
ADPT
C
TRL
AUTO
ENBL
AUTO
PID
Summary of Contents for MICROMEGA CN77000 series
Page 4: ...NOTES ...
Page 19: ...SETUP part 2 11 Dip Switch Settings ...
Page 31: ...Figure 3 2 Flowchart for Input Type OPERATION CONFIGURATION MODE part 3 23 ...
Page 36: ...Figure 3 3 Flowchart for Reading Configuration part 3 OPERATION CONFIGURATION MODE 28 ...
Page 45: ...Figure 3 5 Flowchart for Loop Break OPERATION CONFIGURATION MODE part 3 37 ...
Page 49: ...OPERATION CONFIGURATION MODE part 3 41 Figure 3 6 Flowchart for Output 1 ...
Page 59: ...OPERATION CONFIGURATION MODE part 3 51 Figure 3 7 Flowchart for Output 2 ...
Page 65: ...OPERATION CONFIGURATION MODE part 3 57 Figure 3 8 Flowchart for Ramp Soak ...