part
3
O
PERATION
:
C
ONFIGURATION
M
ODE
80
Command Formats
cont.
AL1CNFG.0
= 0 Disable
AL1CNFG.1
= 0 Absolute
AL1CNFG.2
= 0 Unlatch
AL1CNFG.3
= 0 Normally Open
1 Enable
1 Deviation
1 Latch
1 Normally Closed
AL1CNFG.54
= 00 Above
AL1CNFG.6
= 0 Loop Break Alarm Disable
AL1CNFG.7
= 0 Alarm Power On Enable
01 Below
1 Loop Break Alarm Enable
1 Alarm Power On Disable
10 Hi/Lo
* 11 Band
* Deviation Only
Example:
Set Alarm 1 Enable, Deviation, Unlatch, N.C., Band, Loop Disable, Alarm Power On Enable. The command data is
10111011Bin = BBHex. Send *W09BB.