O
PERATION
:
C
ONFIGURATION
M
ODE
part
3
31
Reading Configuration
cont. (If process was selected)
Display
Action
Response
INPUT SCALE & OFFSET SUBMENU:
Press ENTER
12) Press enter at the
"
INPT
S
C
.0F
"
prompt. Display flashes 1st digit in submenu
"
IN 1
"
Press MAX & MIN
13) Use MAX and MIN buttons to enter
"
IN 1
"
value.
The
"
IN 1
"
value = min. input value * the natural gain.
Example: 4(mA) x 500 = 2000
Press ENTER
14) Display advances to
"
RD 1
"
submenu.
Press MAX & MIN
15) Use MAX and MIN buttons to enter
"
RD 1
"
value.
This value responds to Ò
IN 1
Ó in terms of some meaningful engineering units
Press ENTER
16) Display advances to
"
IN 2
"
submenu.
The
"
IN 2
"
value = max. input value * the natural gain.
Example: 20(mA) x 500 = 10000 (9999)
Press MAX & MIN
17) Use MAX and MIN buttons to enter
"
IN 2
"
value.
Press ENTER
18) Display advances to
"
RD 2
"
submenu.
Press MAX & MIN
19) Use MAX and MIN buttons to enter
"
RD 2
"
value.
Press ENTER
20) Display flashes
"
stored
"
message and advances to
"
Alar 1
"
menu.
This submenu allows the user to scale the meter when in Process Mode and the
above display value is an example for 4-20 mA input (4 to 20 mA = 0000 to 0100%).
RD 2
0100.
IN 2
9999.
RD 1
0000.
IN 1
2000.
INPT
SC.0F
Note
☞
Summary of Contents for MICROMEGA CN77000 series
Page 4: ...NOTES ...
Page 19: ...SETUP part 2 11 Dip Switch Settings ...
Page 31: ...Figure 3 2 Flowchart for Input Type OPERATION CONFIGURATION MODE part 3 23 ...
Page 36: ...Figure 3 3 Flowchart for Reading Configuration part 3 OPERATION CONFIGURATION MODE 28 ...
Page 45: ...Figure 3 5 Flowchart for Loop Break OPERATION CONFIGURATION MODE part 3 37 ...
Page 49: ...OPERATION CONFIGURATION MODE part 3 41 Figure 3 6 Flowchart for Output 1 ...
Page 59: ...OPERATION CONFIGURATION MODE part 3 51 Figure 3 7 Flowchart for Output 2 ...
Page 65: ...OPERATION CONFIGURATION MODE part 3 57 Figure 3 8 Flowchart for Ramp Soak ...