CYCLE TIME SUBMENU:
Press ENTER
15) Display flashes 1st digit of the previous
"
Cycle Time
"
value.
Press MAX & MIN
16) Press MAX and MIN buttons to enter a new
"
Cycle Time
"
value. (1 to 199 seconds).
Press ENTER
17) Display flashes
"
stored
"
message and advances to
"
Ramp & Soak
"
Menu.
A Cycle Time selected between 1 to 199 seconds indicates the total On/Off time of each proportional cycle. For example, a
15 second Cycle Time means that every 15 seconds the output will turn on for part or all of the cycle. For Relay control
outputs, do not select a cycle time of less than 7 seconds or the relays life time will be shortened. For a cycle time of less
than 7 seconds select SSR or DC pulse. Use an external SSR with the DC pulse option for higher current (higher than 1 Amp).
C
Y
C
L
0010
C
Y
C
L
TIME
Note
☞