
ARYAL S2 E DUAL / TRIAL
ENGLISH
EN - 23
Once the previously described conditions are met, follow these guidelines when the
wiring is carried out:
• Always have an individual power circuit specifically for the air conditioner. Always
follow the circuit diagram posted on the inside of the control cover.
• Screws fastening the wiring in the casing of electrical fittings may come loose dur
-
ing transportation. Because loose screws may cause wire burn-out, check that the
screws are tightly fastened.
• Check the specifications for the power source.
• Confirm that electrical capacity is sufficient.
• Confirm that starting voltage is maintained at more than 90 percent of the rated
voltage marked on the name plate.
• Confirm that the cable thickness is as specified in the power source specifications.
• Always install an earth leakage circuit breaker in wet or moist areas.
• The following can be caused by a drop in voltage: vibration of a magnetic switch,
damaging the contact point, broken fuses, and disturbance of normal functioning.
• Disconnection from a power supply must be incorporated into the fixed wiring. It
must have an air gap contact separation of at least 3mm in each active (phase) con-
ductors.
• Before accessing terminals, all supply circuits must be disconnected.
9 - AIR EVACUATION
Air and foreign matter in the refrigerant circuit can cause abnormal rises in pressure, which can damage the
air conditioner, reduce its efficiency, and cause injury.
Use a vacuum pump and manifold gauge to evacuate the refrigerant circuit, removing any non-condensable
gas and moisture from the system.
Evacuation should be performed upon initial installation and when unit is relocated.
BEFORE PERFORMING EVACUATION
•
Check to make sure the connective pipes between the indoor and outdoor units are connected
properly.
•
Check to make sure all wiring is connected.
Before using a manifold gauge and a vacuum pump, read their operation manuals to make sure you know
how to use them properly.
1.
Connect the manifold gauge charge hose to the
service port on the outdoor unit’s low pressure
valve.
2.
Connect the manifold gauge charge hose from
the to the vacuum pump.
3.
Open the Low Pressure side of the manifold
gauge. Keep the High Pressure side closed.
4.
Turn on the vacuum pump to evacuate the system.
5.
Run the vacuum for at least 15 minutes, or until
the Compound Meter reads -76cmHG (-1x105Pa).
6.
Close the manifold gauge Low Pressure valve and turn off the vacuum pump.
7.
Wait for 5 minutes, then check that there has been no change in system pressure.
If there is no change in system pressure, unscrew the cap from the packed valve (high pressure
valve). If there is a change in system pressure, there may be a gas leak.
Evacuation Instructions
Before using a manifold gauge and a vacuum
pump, read their operation manuals to make
sure you know how to use them properly.
Manifold Gauge
Compound gauge
-76cmHg
Low pressure valve
High pressure valve
Charge hose
Charge hose
Vacuum pump
Pressure gauge
Low pressure valve
1. Connect the manifold gauge’s charge hose
to the service port on the outdoor unit’s low
pressure valve.
2. Connect the manifold gauge’s charge hose
from the to the vacuum pump.
3. Open the Low Pressure side of the manifold
gauge. Keep the High Pressure side closed.
4. Turn on the vacuum pump to evacuate the system.
5. Run the vacuum for at least 15 minutes, or until
the Compound Meter reads -76cmHG (-1x105Pa).
6. Close the manifold gauge’s Low Pressure valve
and turn off the vacuum pump.
7. Wait for 5 minutes, then check that there has
been no change in system pressure.
NOTE:
If there is no change in system pressure,
unscrew the cap from the packed valve (high
pressure valve). If there is a change in system
pressure, there may be a gas leak.
8. Insert hexagonal wrench into the packed valve
(high pressure valve) and open the valve by
turning the wrench 1/4 counterclockwise.
Listen for gas to exit the system, then close the
valve after 5 seconds.
Flare nut
Cap
Valve body
Valve stem
9. Watch the Pressure Gauge for one minute to make
sure that there is no change in pressure. It should
read slightly higher than the atmospheric pressure.
10.Remove the charge hose from the service port.
11. Using hexagonal wrench, fully open both the
high pressure and low pressure valves.
OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal
wrench until it hits against the stopper.
DO NOT
try to force the valve to open further.
12.Tighten valve caps by hand, then tighten it
using the proper tool.
13.If the outdoor unit uses all vacuum valves,
and the vacuum position is at the main valve,
the system is not connected with the indoor
unit. The valve must be tightened with a
screw nut. Check for gas leaks before
operation to prevent leakage.
Air Evacuation
Preparations and Precautions
Air and foreign matter in the refrigerant circuit can
cause abnormal rises in pressure, which can damage
the air conditioner, reduce its efficiency, and cause
injury. Use a vacuum pump and manifold gauge to
evacuate the refrigerant circuit, removing any
non-condensable gas and moisture from the system.
Evacuation should be performed upon initial
installation and when unit is relocated.
BEFORE PERFORMING EVACUATION
Check to make sure the connective pipes
between the indoor and outdoor units
are connected properly .
Check to make sure all wiring is connected
Air Evacuation
Summary of Contents for ARYAL S2 E
Page 2: ......
Page 190: ...EL 2 0 1 1 OL PIA SPLENDID 2 3 4 5 6 7 8 9 10...
Page 198: ...EL 10 4 3 COOL HEAT TIMERON 5 5 1 5 2 3...
Page 199: ...ARYAL S2 E DUAL TRIAL EL 11 7 C 5 3 1 a 3 b 4 10 2 COOL...
Page 200: ...EL 12 3 4 5 6 FAN 7 80 8 9 3 10 6 Q ty pc 2 4 1 Q ty pc 5 8 A 5 8...
Page 209: ...ARYAL S2 E DUAL TRIAL EL 21 7 8 9 8 90 110 1 32 ohms 0 OFF...
Page 213: ...ARYAL S2 E DUAL TRIAL EL 25 9 1 1 2M 2 4 3 1 2 A B C A B DUAL A B C TRIAL 9 2 a i 1 2 3 4 a...
Page 215: ......
Page 216: ...264710B...