
ARYAL S2 E DUAL / TRIAL
ENGLISH
EN - 19
3.
Make sure that the pipe is cut at a perfect 90°
angle.
DO NOT DEFORM PIPE WHILE CUTTING.
Be extra careful not to damage, dent, or
deform the pipe while cutting. This will
drastically reduce the heating efficiency
of the unit.
7.6.2 - Step 2: Remove burrs
Burrs can affect the air-tight seal of refrigerant piping
connection. They must be completely removed.
1.
Hold the pipe at a downward angle to prevent
burrs from falling into the pipe.
2.
Using a reamer or deburring tool, remove all burrs
from the cut section of the pipe.
7.6.3 - Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
1.
After removing burrs from cut pipe, seal the ends
with PVC tape to prevent foreign materials from
entering the pipe.
2.
Sheath the pipe with insulating material.
3.
Place flare nuts on both ends of pipe. Make sure
they are facing in the right direction, because you
can’t put them on or change their direction after
flaring.
Refrigerant Piping
Connection
Refrigerant Piping Connection
Flare nut
Copper pipe
When connecting refrigerant piping,
do not
let substances or gases other than the specified
refrigerant enter the unit. The presence of other
gases or substances will lower the unit’s capacity,
and can cause abnormally high pressure in the
refrigeration cycle. This can cause explosion and
injury.
Step 1: Cut pipes
When preparing refrigerant pipes, take extra
care to cut and flare them properly. This will
ensure efficient operation and minimize the
need for future maintenance.
1. Measure the distance between the indoor
and outdoor units.
CAUTION
•
The branching pipe must be installed
horizontally. An angle of more than 10° may
cause malfunction.
•
DO NOT
install the connecting pipe until
both indoor and outdoor units have been
installed.
•
Insulate both the gas and liquid piping to
prevent water leakage.
Connection Instructions –
Refrigerant Piping
2.
Using a pipe cutter, cut the pipe a little longer
than the measured distance.
3. Make sure that the pipe is cut at a perfect 90°
angle.
DO NOT DEFORM PIPE
WHILE CUTTING
Be extra careful not to damage, dent, or deform
the pipe while cutting. This will drastically reduce
the heating efficiency of the unit.
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight
seal.
1. After removing burrs from cut pipe, seal
the ends with PVC tape to prevent foreign
materials from entering the pipe.
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe.
Make sure they are facing in the right
direction, because you can’t put them on
or change their direction after flaring.
Step 2: Remove burrs.
Burrs can affect the air-tight seal of refrigerant
piping connection. They must be completely
removed.
1. Hold the pipe at a downward angle to
prevent burrs from falling into the pipe.
2. Using a reamer or deburring tool, remove
all burrs from the cut section of the pipe.
Pipe
Reamer
Point down
Oblique Rough Warped
90°
NOTE:
For quick-connect models, please
refer to the internal machine manual for the
installation method of the connecting pipe.
The external machine manual does not
repeat the instructions.
Refrigerant Piping
Connection
Refrigerant Piping Connection
Flare nut
Copper pipe
When connecting refrigerant piping,
do not
let substances or gases other than the specified
refrigerant enter the unit. The presence of other
gases or substances will lower the unit’s capacity,
and can cause abnormally high pressure in the
refrigeration cycle. This can cause explosion and
injury.
Step 1: Cut pipes
When preparing refrigerant pipes, take extra
care to cut and flare them properly. This will
ensure efficient operation and minimize the
need for future maintenance.
1. Measure the distance between the indoor
and outdoor units.
CAUTION
•
The branching pipe must be installed
horizontally. An angle of more than 10° may
cause malfunction.
•
DO NOT
install the connecting pipe until
both indoor and outdoor units have been
installed.
•
Insulate both the gas and liquid piping to
prevent water leakage.
Connection Instructions –
Refrigerant Piping
2.
Using a pipe cutter, cut the pipe a little longer
than the measured distance.
3. Make sure that the pipe is cut at a perfect 90°
angle.
DO NOT DEFORM PIPE
WHILE CUTTING
Be extra careful not to damage, dent, or deform
the pipe while cutting. This will drastically reduce
the heating efficiency of the unit.
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight
seal.
1. After removing burrs from cut pipe, seal
the ends with PVC tape to prevent foreign
materials from entering the pipe.
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe.
Make sure they are facing in the right
direction, because you can’t put them on
or change their direction after flaring.
Step 2: Remove burrs.
Burrs can affect the air-tight seal of refrigerant
piping connection. They must be completely
removed.
1. Hold the pipe at a downward angle to
prevent burrs from falling into the pipe.
2. Using a reamer or deburring tool, remove
all burrs from the cut section of the pipe.
Pipe
Reamer
Point down
Oblique Rough Warped
90°
NOTE:
For quick-connect models, please
refer to the internal machine manual for the
installation method of the connecting pipe.
The external machine manual does not
repeat the instructions.
Refrigerant Piping
Connection
Refrigerant Piping Connection
Flare nut
Copper pipe
When connecting refrigerant piping,
do not
let substances or gases other than the specified
refrigerant enter the unit. The presence of other
gases or substances will lower the unit’s capacity,
and can cause abnormally high pressure in the
refrigeration cycle. This can cause explosion and
injury.
Step 1: Cut pipes
When preparing refrigerant pipes, take extra
care to cut and flare them properly. This will
ensure efficient operation and minimize the
need for future maintenance.
1. Measure the distance between the indoor
and outdoor units.
CAUTION
•
The branching pipe must be installed
horizontally. An angle of more than 10° may
cause malfunction.
•
DO NOT
install the connecting pipe until
both indoor and outdoor units have been
installed.
•
Insulate both the gas and liquid piping to
prevent water leakage.
Connection Instructions –
Refrigerant Piping
2.
Using a pipe cutter, cut the pipe a little longer
than the measured distance.
3. Make sure that the pipe is cut at a perfect 90°
angle.
DO NOT DEFORM PIPE
WHILE CUTTING
Be extra careful not to damage, dent, or deform
the pipe while cutting. This will drastically reduce
the heating efficiency of the unit.
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight
seal.
1. After removing burrs from cut pipe, seal
the ends with PVC tape to prevent foreign
materials from entering the pipe.
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe.
Make sure they are facing in the right
direction, because you can’t put them on
or change their direction after flaring.
Step 2: Remove burrs.
Burrs can affect the air-tight seal of refrigerant
piping connection. They must be completely
removed.
1. Hold the pipe at a downward angle to
prevent burrs from falling into the pipe.
2. Using a reamer or deburring tool, remove
all burrs from the cut section of the pipe.
Pipe
Reamer
Point down
Oblique Rough Warped
90°
NOTE:
For quick-connect models, please
refer to the internal machine manual for the
installation method of the connecting pipe.
The external machine manual does not
repeat the instructions.
4.
Remove PVC tape from ends of pipe when ready
to perform flaring work.
5.
Position the pipe into the flare form. The end of
the pipe must extend beyond the flare form.
6.
Turn the handle of the flaring tool clockwise until
the pipe is fully flared.
4. Remove PVC tape from ends of pipe when
ready to perform flaring work.
5. Clamp flare form on the end of the pipe. The
end of the pipe must extend beyond the flare
form.
Flare form
Pipe
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool
clockwise until the pipe is fully flared. Flare
the pipe in accordance with the dimensions .
PIPING EXTENSION BEYOND FLARE FORM
8. Remove the flaring tool and flare form,
then inspect the end of the pipe for cracks
and even flaring.
Pipe
gauge
Tightening
torque
Flare dimension (A)
(Unit: mm/Inch)
Flare shape
Min.
Max.
Ø 6.4
R0.4~0.8
45
°±
2
90
°
±
4
A
Ø 9.5
Ø 12.7
Ø 15.9
Ø 19.1
Ø 22
65-67 N.m
(663-683 kgf.cm)
23.2/0.91
23.7/0.93
75-85N.m
(765-867 kgf.cm)
26.4/1.04
26.9/1.06
18-20 N.m
(183-204 kgf.cm)
8.4/0.33
8.7/0.34
25-26 N.m
(255-265 kgf.cm)
13.2/0.52
13.5/0.53
35-36 N.m
(357-367 kgf.cm)
16.2/0.64
16.5/0.65
45-47 N.m
(459-480 kgf.cm)
19.2/0.76
19.7/0.78
Step 4: Connect pipes
Connect the copper pipes to the indoor unit first,
then connect it to the outdoor unit. You should
first connect the low-pressure pipe, then the
high-pressure pipe.
1. When connecting the flare nuts, apply a thin
coat of refrigeration oil to the flared ends of
the pipes.
2. Align the center of the two pipes that you will
connect.
Indoor unit tubing
Flare nut
Pipe
3. Tighten the flare nut as tightly as possible
by hand.
4. Using a spanner, grip the nut on the unit
tubing.
5. While firmly gripping the nut, use a torque
wrench to tighten the flare nut according to
the torque values in above table.
NOTE:
Use both a spanner and a torque
wrench when connecting or disconnecting
pipes to/from the unit.
CAUTION
•
Ensure to wrap insulation around the piping.
Direct contact with the bare piping may
result in burns or frostbite.
•
Make sure the pipe is properly connected.
Over tightening may damage the bell
mouth and under tightening may lead to
leakage.
Refrigerant Piping
Connection
Summary of Contents for ARYAL S2 E
Page 2: ......
Page 190: ...EL 2 0 1 1 OL PIA SPLENDID 2 3 4 5 6 7 8 9 10...
Page 198: ...EL 10 4 3 COOL HEAT TIMERON 5 5 1 5 2 3...
Page 199: ...ARYAL S2 E DUAL TRIAL EL 11 7 C 5 3 1 a 3 b 4 10 2 COOL...
Page 200: ...EL 12 3 4 5 6 FAN 7 80 8 9 3 10 6 Q ty pc 2 4 1 Q ty pc 5 8 A 5 8...
Page 209: ...ARYAL S2 E DUAL TRIAL EL 21 7 8 9 8 90 110 1 32 ohms 0 OFF...
Page 213: ...ARYAL S2 E DUAL TRIAL EL 25 9 1 1 2M 2 4 3 1 2 A B C A B DUAL A B C TRIAL 9 2 a i 1 2 3 4 a...
Page 215: ......
Page 216: ...264710B...