5 Parameter
BU 0180 en-4118
89
For this purpose, the device is equipped with a power supply which generates the 24 V DC control
voltage that is required by applying the mains voltage (see
Section 2.4.2 "Electrical connection of
power unit").
Limited adaptations of individual functions of the relevant devices can be implemented via
DIP switches. Access to the parameters of the device is essential for all other adaptations.
It should
be noted that the hardware configuration (DIP switches) has priority over configuration via
software (parameterisation).
Every frequency inverter is pre-configured for a NORD motor with the same power output in the
factory. All parameters can be adjusted "online". Four switchable parameter sets are available during
operation. The scope of the parameters to be displayed can be influences using the Supervisor
Parameter
P003
.
The relevant parameters for the device are described in the following. Explanation of parameters
which relate to the field bus options or special functionality can be found in the respective
supplementary manuals.
Information
SK PAR-3H ParameterBox
The SK PAR-3H ParameterBox must have at least software version
4.4 R2
.
The individual parameters are functionally combined into groups. The first digit of the parameter
number indicates the assignment to a
menu group
:
Menu group
No.
Master function
Operating displays
(P0--)
Display of parameters and operational values
Basic parameters
(P1--)
Basic device settings, e.g. on/off switching behaviour.
Motor data
(P2--)
Electrical settings for the motor (motor current or start voltage (start-off
voltage))
PLC
(P3--)
Settings for the integrated PLC
Control terminals
(P4--)
Assignment of functions for the inputs and outputs
Extra parameters
(P5--)
Priority monitoring functions and other parameters
Information
(P7--)
Display of operating values and status messages
Information
Factory settings P523
The factory setting of the entire parameter set can be loaded at any time using parameter
P523
. For example,
this can be useful during commissioning if it is not known which device parameters were changed earlier and
could therefore influence the operating behaviour of the drive in an undesirable way.
The restoration of the factory settings (
P523
) normally affects all parameters. This means that all motor data must
subsequently be checked or reconfigured. However, parameter
P523
also provides a facility for excluding the
motor data or the parameters relating to bus communication when the factory settings are restored.
To save the current device settings, these can be transferred to a ParameterBox memory beforehand
(see
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...