5 Parameter
BU 0180 en-4118
139
P525
[-01]
...
[-03]
Load control max
(Load monitoring maximum value)
S
P
1 ... 400 % / 401
{ all 401 }
Selection of up to 3 auxiliary values:
[-01] = Auxiliary value 1
[-02] = Auxiliary value 2
[-03] = Auxiliary value 3
Maximum load torque value.
Setting of the upper limit of load monitoring. Up to 3 values can be specified. Prefixes are not
taken into account, only the integer values are processed (motor / generator torque, right/left
rotation). The array elements [-01], [-02] and [-03] of parameters (P525) … (P527), or the entries
which are made there always belong together.
401 = OFF
Means that the function is switched off. No monitoring is performed. This is also the
basic setting for the FI.
P526
[-01]
...
[-03]
Load control min
(Load monit
oring, minimum value)
S
P
0 ... 400 %
{ all 0 }
Selection of up to 3 auxiliary values:
[-01] = Auxiliary value 1
[-02] = Auxiliary value 2
[-03] = Auxiliary value 3
Minimum load torque.
Setting of the lower limit value of load monitoring. Up to 3 values can be specified. Prefixes are
not taken into account, only the integer values are processed (motor / generator torque, right/left
rotation). The array elements [-01], [-02] and [-03] of parameters (P525) … (P527), or the entries
which are made there always belong together.
0 = OFF
Means that the function is switched off. No monitoring is performed. This is also the
basic setting for the FI.
P527
[-01]
...
[-03]
Load control freq.
(Load monitoring frequency)
S
P
0.0 ... 400.0 Hz
{ all 25.0 }
Selection of up to 3 auxiliary values:
[-01] = Auxiliary value 1
[-02] = Auxiliary value 2
[-03] = Auxiliary value 3
Auxiliary frequency values
Definition of up to 3 frequency points, which define the monitoring range for load monitoring. The
auxiliary frequency values do not need to be entered in order of size. Prefixes are not taken into
account, only the integer values are processed (motor / generator torque, right/left rotation). The
array elements [-01], [-02] and [-03] of parameters (P525) … (P527), or the entries which are
made there always belong together.
P528
Load control delay
(Load monitoring delay)
S
P
0.10 ... 320.00 s
{ 2.00 }
Parameter (P528) defines the delay time for which an error message ("E12.5") is suppressed on
infringement of the defined monitoring range ((P525) … (P527)). A warning ("C12.5") is triggered
after half of this time has elapsed.
According to the selected monitoring mode (P529) an error message can also be generally
suppressed.
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...