6 Operating status messages
BU 0180 en-4118
167
C003
3.0
Overcurrent, I
2
t limit
Warning: Inverter: I
2
t limit has triggered, e.g. > 1.3 x I
n
for
60s (please also note P504)
• Continuous overload at FI output
3.1
Overcurrent, chopper I
2
t
Warning: I
2
t limit for the brake chopper has triggered, 1.3x
value attained for 60s (also note P554, if present, as well as
P555, P556, P557)
• Avoid overload of brake resistance
3.5
Torque current limit
Warning: Torque current limit reached
•
Check
(P112)
3.6
Current limit
Warning: Current limit reached
•
Check
(P536)
C004
4.1
Overcurrent measurement
"Overcurrent measurement"
Warning: pulse switch off is active
The limit for activation of pulse switch off (P537) has been
reached (only possible if P112 and P536 are switched off)
• FI is overloaded
• Drive sluggish, insufficiently sized
• Ramps (P102/P103) too steep -> Increase ramp time
• Check motor data (P201 … P209)
• Switch off slip compensation (P212)
C008
8.0
Parameter loss
Warning:
One of the cyclically saved messages such
as
operating hours
or
enabling time
could not be
saved successfully.
The warning disappears as soon as saving can be
successfully performed.
C012
12.1
Limit moto./Customer
"Drive switch
-
off limit"
Warning: 80 % of the drive switch-off limit (P534 [-01]) has
been exceeded.
• Reduce load on motor
• Set higher value in (P534 [-01]).
12.2
Limit gen.
"Generator switch
-
off limit"
Warning: 80 % of the generator switch-off limit (P534 [-02])
has been reached.
• Reduce load on motor
• Set higher value in (P534 [-02]).
12.3
Torque limit
Warning: 80 % of the limit from the potentiometer or the
setpoint source has been reached. P400 = 12
12.4
Current limit
Warning: 80 % of the limit from the potentiometer or the
setpoint source has been reached. P400 = 14
12.5
Load monitor
Warning due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
• Adjust load.
• Change limit values ((P525) ... (P527)).
• Increase delay time (P528).
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...