NORDAC BASE (SK 180E / SK 190E) – Users Manual for Frequency Inverters
124
BU 0180 en-4118
Value Function
Description
Signal
04
1
Fixed frequency 1
The frequency from P465 [01] is added to the actual setpoint
value.
High
05
1
Fixed frequency 2
The frequency from P465 [02] is added to the actual setpoint
value.
High
06
1
Fixed frequency 3
The frequency from P465 [03] is added to the actual setpoint
value.
High
07
1
Fixed frequency 4
The frequency from P465 [04] is added to the actual setpoint
value.
High
If several fixed frequencies are actuated at the same time, then they are added with the correct sign. The
analogue setpoint (P400) and, if necessary, the minimum frequency (P104) are also added.
08
4
Parameter set changeover
"Parameter set changeover 1
"
Selection of active parameter set 1…4 - first bit.
High
09
Hold frequency
During the acceleration or deceleration phase, a Low level will
cause the actual output frequency to "Halt". A High level allows
the ramp to continue.
Low
10
2
Disable voltage
(coast to stop)
The FI output voltage is switched off; the motor runs down
freely.
Low
11
2
Emergency stop
The FI reduces the frequency according to the programmed fast
stop time P426.
Low
12
2
Fault acknowledgement
Fault acknowledgement with an external signal. If this function
is not programmed, a fault can also be acknowledged by a low
enable setting (P506).
0
1
Flank
13
2
PTC resistor input
Only with the use of a temperature monitor (bimetallic switching
contact). Switch-off delay = 2sec, warning after 1 sec.
High
14
2, 3
Remote control
With bus system control, Low level switches the control to
control via control terminals.
High
15
Jog frequency
1
The frequency value from (P113) can also be set directly using
the HIGHER/LOWER buttons with a controller, SimpleBox or
ParameterBox and stored in (P113) using the OK button.
If the device is operating with inching frequency, any bus
actuation that may be active is deactivated.
High
16
Motor potentiometer
Similar to
09
, but the frequency is not maintained below the
minimum frequency P104 and above the maximum frequency
P105.
Low
17
4
ParaSet Switching
2
"Parameter set changeover 2"
Selection of active parameter set 1…4 - second bit.
High
18
2
Watchdog
Input must see a High flank cyclically (P460), otherwise error
E012 will cause a shutdown. Function starts with the 1st high
flank.
0
1
Flank
19
Setpoint 1 on/off
Analogue input switch-on and switch-off 1/2 (high = ON) of the
first I/O extension. The Low signal sets the analogue input to
0 % which does not lead to shutdown when the minimum
frequency (P104) > than the absolute minimum frequency
(P505).
High
20
Setpoint 2 on/off
High
21
... 28 reserved
29
Enable SetpointBox
The release signal is provided by the
Simple SetpointBox
(setpoint box) SK SSX-3A, whereby the Box must be operated
in
IO-S
mode.
High
30
Disable PID
Switching the PID controller / process controller function on and
off (high = ON)
High
31
2
Disable right rotation
Blocks the >Enable right/left< via a digital Input or bus
actuation. Does not depend on the actual direction of rotation of
the motor (e.g. following negated setpoint).
Low
32
2
Disable left rotation
Low
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...