5 Parameter
BU 0180 en-4118
93
5.2.1 Operating displays
Abbreviations used:
•
FI
= Frequency inverter
•
SW
= Software version, stored in P707.
•
S = Supervisor parameters
are visible or hidden depending on P003.
Parameter
{factory setting}
Setting value / Description / Note
Supervisor
Parameter
set
P000
Operating display
(Operating parameter display)
0.01 ... 9999
In ParameterBoxes with 7-segment displays (e.g. SimpleBox) the operating value which is selected
in P001 is displayed
online
.
Important information about the operating status of the drive can be read out as required.
P001
Display selection
(Display selection)
0 ... 65
{ 0 }
Selection of operating display of a parametrisation box with 7-segment display (e.g.: SimpleBox)
0 =
Actual frequency [Hz]
Currently supplied output frequency
1 =
Speed [rpm]
Calculated speed
2 =
Target frequency [Hz]
Output frequency that corresponds to the pending setpoint. This
need not correspond with the current output frequency.
3 =
Current [A]
Current measured output current
4 =
Actual torque current [A]:
Torque-forming output current
5 =
Voltage [V AC]
Current alternating voltage present at the device output
6 =
Link voltage [V DC]
The
Link voltage [Vdc]
is the FI-internal DC voltage. Amongst other
things, this depends on the level of the mains voltage.
7 =
cos Phi
Current calculated value of the power factor
8 =
Apparent power [kVA]
Calculated current apparent power
9 =
Effective power [kW]
Calculated current effective power
10 =
Torque [%]
Calculated current torque
11 =
Field [%]
Calculated current field in motor
12 =
Hours of operation [h]
Time for which main voltage present at device
13 =
Operating time Enable [h]
"Enabled operating hours"
is the time for which the device was
enabled.
14 =
Analogue input 1 [%]
Current value that is present at analogue input 1 of the device
15 =
Analogue input 2 [%]
Current value that is present at analogue input 2 of the device
16 =
… 18
Reserved
19 =
Heat sink temperature [°C]
Current temperature of the heat sink
20 =
Actual utilisation of motor
[%]
Average motor utilisation, based on the known motor data
(P201...P209).
21 =
Brake resistor utilisation
[%]
"Braking resistor utilisation"
is the average braking resistor load,
based on the known resistance data (P556...P557).
22 =
Interior temperature [°C]
Current interior temperature of device
(SK 54
xE / SK
2xxE)
23 =
Motor temperature
Measured via KTY-84
24 =
… 29
Reserved
30 =
Present Target MP-S [Hz]
"Current motor potentiometer function setpoint with storage"
.
(P420…=71/72). The nominal value can be read out with this
function or pre-set (without the drive running).
31 =
… 39
Reserved
40 =
PLC control box value
Visualisation mode for PLC communication
41 =
… 59
Reserved
60 =
R stator ident
Stator resistance determined by means of measurement (P220)
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...