6 Operating status messages
BU 0180 en-4118
165
12.5
Load monitor
Switch-off due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
• Adjust load.
• Change limit values ((P525) ... (P527)).
• Increase delay time (P528).
• Change monitoring mode (P529).
12.8
AI minimum
„Analog
ue
In minimum“
Switch-off due to undershooting of the 0% adjustment value
(P402) with setting (P401) "0-10V with switch-off on error 1"
or "....2"
12.9
AI maximum
„Analog
ue
In m
aximum
“
Switch-off due to overshooting of the 100% adjustment
value (P402) with setting (P401) "0-10V with switch-off on
error 1" or "....2"
E013
13.2
Shut-down monitoring
The slip error monitoring was triggered; the motor could not
follow the setpoint.
• Check motor data P201-P209! (important for current
controllers)
• Check motor circuit
• Check encoder settings P300 and following in servo
mode
• Increase setting value for torque limit in P112
• Increase setting value for current limit in P536
• Check deceleration time P103 and extend if
necessary
E015
---
Reserved
E016
16.0
Motor phase error
A motor phase is not connected.
• Check P539
• Check motor connection
16.1
Magnetisation current
monitoring
"Magnetisation current
monitoring"
Required exciting current not achieved at moment of switch-
on.
• Check P539
•
Check motor connection
E019
19.0
Parameter identification
"Parameter identification"
Automatic identification of the connected motor was
unsuccessful
• Check motor connection
• Check preset motor data (P201 … P209)
• PMSM – CFC Closed Loop Operation: Rotor position
of motor incorrect in relation to incremental encoder
Perform determination of rotor position (initial enable
after a "Mains on" only with motor stationary (P330)
19.1
Star / Delta circuit incorrect
"Motor star / delta circuit
incorrect"
E020
E021
20.0
Reserved
System error in program execution, triggered by EMC
interference.
•
Observe wiring guidelines
•
Use additional external mains filter.
•
FI must be very well earthed.
20.1
Watchdog
20.2
Stack overflow
20.3
Stack underflow
20.4
Undefined opcode
20.5
Protected Instruct.
"Protected Instruction"
20.6
Illegal word access
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...