5 Parameter
BU 0180 en-4118
131
P480
[-01]
...
[-12]
Function BusIO In Bits
(Bus I/O In Bits function)
0 ... 80
{ [-01] = 01 }
{ [-02] = 02 }
{ [-03] = 05 }
{ [-04] = 12 }
{ [-05...-12] = 00 }
The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions (P420).
With devices with an integrated AS interface, the I/O bits can be used by the interface itself
(bit 0 ... 3) or in combination with I/O extensions (SK xU4-IOE) (bits 4 … 7 and bits 0 … 3).
With
AS-
i devices, the priority is AS
-
i. In this case BUS IO BITs 1 … 4 cannot be used by the 2nd. IO
extension.
[-01] = Bus / AS-i Dig In1
(Bus IO In Bit 0 + AS-i 1 or DI 1 of the
second
SK xU4
-
IOE (DigIn 09))
[-02] = Bus / AS-i Dig In2
(Bus IO In Bit 1 + AS-i 2 or DI 2 of the
second
SK xU4
-
IOE (DigIn 10))
[-03] = Bus / AS-i Dig In3
(Bus IO In Bit 2 + AS-i 3 or DI 3 of the
second
SK xU4
-
IOE (DigIn 11))
[-04] =
Bus / AS-i Dig In4
(Bus IO In Bit 3 + AS-i 4 or. DI 4 of the
second
SK xU4
-
IOE (DigIn 12))
[-05] =
Bus / IOE Dig In1
(Bus IO In Bit 4 + DI 1 of the
first
SK xU4
-
IOE (DigIn 05))
[-06] =
Bus / IOE Dig In2
(Bus IO In Bit 5 + DI 2 of the
first
SK xU4
-
IOE (DigIn 06))
[-07] =
Bus / IOE Dig In3
(Bus IO In Bit 6 + DI 3 of the
first
SK xU4
-
IOE (DigIn 07))
[-08] =
Bus / IOE Dig In4
(Bus IO In Bit 7 + DI 4 of the
first
SK xU4
-
IOE (DigIN 08))
[-09] =
Flag 1
1)
[-10] =
Flag 2
1)
[-11] =
Bit 8 BUS control word
[-12] =
Bit 9 BUS control word
The possible functions for the bus In bits can be found in the table of functions for the digital
inputs in parameter (P420). Functions {14} "Remote control" and {29} "Enable SetpointBox" are
not possible.
1) The flag function is only possible with control via control terminals.
P481
[-01]
...
[-10]
Function
BusIO Out Bits
(Function of Bus I/O Out Bits)
0 ... 40
{ [-01] = 18 }
{ [-02] = 08 }
{ [-03] = 30 }
{ [-04] = 31 }
{ [-05...-10] = 00 }
The bus I/O Out bits are perceived as multi-function relay outputs. They can be set to the same
functions (P434).
With devices with in integrated AS interface, the I/O bits can be used by the interface itself
(bit 0 ... 3) or in combination with I/O extensions (SK xU4-IOE) (bits 4 … 5 and flags 1 … 2).
[-01] =
Bus / AS-i Dig Out1
(Bus IO Out Bit 0 + AS-i 1)
[-02] =
Bus / AS-i Dig Out2
(Bus IO Out Bit 1 + AS-i 2)
[-03] =
Bus / AS-i Dig Out3
(Bus IO Out Bit 2 + AS-i 3)
[-04] =
Bus / AS-i Dig Out4
(Bus IO Out Bit 3 + AS-i 4)
[-05] =
Bus / IOE Dig Out1
(Bus IO Out Bit 4 + DO 1 of the
first
SK xU4
-
IOE (DigOut 02))
[-06] =
Bus / IOE Dig Out2
(Bus IO Out Bit 5 + DO 2 of the
first
SK xU4
-
IOE (DigOut 03))
[-07] =
Bus / 2nd IOE Dig Out1
(Flag1
1)
+ DO 1 of the
second
SK xU4
-
IOE (DigOut 04))
[-08] =
Bus / 2nd IOE Dig Out2
(Flag2
1)
+ DO 2 of the
second
SK xU4
-
IOE (DigOut 05))
[-09] =
Bit 10 BUS status word
[-10] =
Bit 13 BUS status word
The possible functions for the Bus Out Bits can be found in the table of functions for the digital
outputs (P434).
1) The flag function is only possible with control via control terminals.
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...