NORDAC BASE (SK 180E / SK 190E) – Users Manual for Frequency Inverters
198
BU 0180 en-4118
8.8.3 100 Hz characteristic curve (only 400 V devices)
(
Variation 01:20)
An operating point 100 Hz/400 V can be
selected for a greater speed adjustment
range with up to a ratio of 1:20. Special
motor data is required in this case (see
below) that differs from the normal 50 Hz
data. It must be ensured in this case that a
constant torque is generated across the
entire adjustment range but that it is smaller
than the nominal torque for 50 Hz operation.
The advantage, in addition to the greater
speed adjustment range, is the improved
motor temperature behaviour. An external
fan is not absolutely essential for smaller
output speed ranges.
Kennlinie 100 Hz (4-poliger Motor)
0
0,2
0,4
0,6
0,8
1
1,2
0
10
20
30
40
50
60
70
80
90 100
Frequenz / Hz
M/Mn
M/M
N
P/P
N
0
1445
2890
Frequency
[Hz]
Speed
[rpm]
Figure 23: 100 Hz characteristic curve
NOTE: The following motor data applies for standard motors with a 230 / 400 V winding. It must
be noted that this information may change slightly because the motors are subject to certain
tolerances. It is recommended that the resistance of the connected motor is measured by the
frequency inverter (P208 / P220).
Motor
(IE1)
SK …
Frequency
inverter
SK 1x0E-…
M
N
*
[Nm]
Parameterisation data of frequency inverter
F
N
[Hz]
n
N
[min-1]
I
N
[A]
U
N
[V]
P
N
[kW]
cos
ϕ
Y/Δ
R
St
[
Ω
]
63S/4
250-340-B
0,90
100
2880
0,95
400
0,25
0,63
Δ
47.37
63L/4
370-340-B
1,23
100
2895
1,07
400
0,37
0,71
Δ
39.90
71L/4
550-340-B
1.81
100
2900
1.59
400
0.55
0.72
Δ
22.85
80S/4
750-340-B
2.46
100
2910
2.0
400
0.75
0.72
Δ
15.79
80L/4
111-340-B
3.61
100
2910
2.8
400
1.1
0.74
Δ
10.49
90S/4
151-340-B
4.90
100
2925
3.75
400
1.5
0.76
Δ
6.41
90L/4
221-340-B
7.19
100
2920
4.96
400
2.2
0.82
Δ
3.99
* at rated point
Motor
(IE2)
SK …
Frequency
inverter
SK 1x0E-…
M
N
*
[Nm]
Parameterisation data of frequency inverter
F
N
[Hz]
n
N
[min-1]
I
N
[A]
U
N
[V]
P
N
[kW]
cos
ϕ
Y/Δ
R
St
[
Ω
]
80SH/4
750-340-B
2.44
100
2930
1.9
400
0.75
0.7
Δ
9.34
80LH/4
111-340-B
3.60
100
2920
2.56
400
1.1
0.73
Δ
6.3
90SH/4
151-340-B
4.89
100
2930
3.53
400
1.5
0.79
Δ
4.96
90LH/4
221-340-B
7.18
100
2925
4.98
400
2.2
0.79
Δ
3.27
* at rated point
100 Hz characteristic curve (4-pole motor)
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...