P201
Nominal motor frequency
(Nominal motor frequency)
S
P
10.0 ... 399.9 Hz
{ see information }
The motor nominal frequency determines the V/f break point at which the FI supplies the nominal
voltage (P204) at the output.
Information
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.
P202
Nominal motor speed
(Nominal motor speed)
S
P
150 ... 24000 rpm
{ see information }
The nominal motor speed is important for the correct calculation and control of the motor slip and
the speed display (P001 = 1).
Information
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.
P203
Nominal motor current
(Nominal motor current)
S
P
0.1 ... 1000.0 A
{ see information }
The nominal motor current is a decisive parameter for the current vector control.
Information
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.
P204
Nominal motor voltage
(Nominal motor voltage)
S
P
100 ... 800 V
{ see information }
The >Nominal voltage< matches the mains voltage to the motor voltage. In combination with the
nominal frequency, the voltage/frequency characteristic curve is produced.
Information
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.
P205
Nominal motor power
(Nominal motor power)
P
0.00 ... 250.00 kW
{ see information }
The motor nominal power controls the motor set via P200.
Information
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.
P206
Motor cos phi
(Motor cos
ϕ
)
S
P
0.50 ... 0.95
{ see information }
The motor cos
ϕ
is a decisive parameter for the current vector control.
Information
Default setting
The default setting is dependent upon the FI nominal power and the setting in P200.
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...