5 Parameter
BU 0180 en-4118
133
P483
[-01]
...
[-10]
Hyst. BusIO Out Bits
(Hysteresis of Bus I/O Out Bits
)
S
1 … 100 %
{ all 10 }
Difference between switch-on and switch-off point to prevent oscillation of the output signal.
[-01] =
Bus / AS-i Dig Out1
(Bus IO Out Bit 0 + AS-i 1)
[-02] =
Bus / AS-i Dig Out2
(Bus IO Out Bit 1 + AS-i 2)
[-03] =
Bus / AS-i Dig Out3
(Bus IO Out Bit 2 + AS-i 3)
[-04] =
Bus / AS-i Dig Out4
(Bus IO Out Bit 3 + AS-i 4)
[-05] =
Bus / IOE Dig Out1
(Bus IO Out Bit 4 + DO 1 of the
first
SK xU4
-
IOE (DigOut 02))
[-06] =
Bus / IOE Dig Out2
(Bus IO Out Bit 5 + DO 2 of the
first
SK xU4
-
IOE (DigOut 03))
[-07] =
Bus / 2nd IOE Dig Out1
(Flag1 + DO 1 of the
second
SK xU4
-
IOE (DigOut 04))
[-08] =
Bus / 2nd IOE Dig Out2
(Flag2 + DO 2 of the
second
SK xU4
-
IOE (DigOut 05))
[-09] =
Bit 10 BUS status word
[-10] =
Bit 13 BUS status word
NOTE:
Details for the use of the relevant bus systems can be found in the applicable supplementary bus
manual.
5.2.6 Additional parameters
Parameter
{factory setting}
Setting value / Description / Note
Supervisor
Parameter set
P501
[-01]
...
[-20]
Inverter name
(Inverter name)
A…Z
(char)
{ 0 }
Free input of a designation (name) for the device (max. 20 characters). With this, the frequency
inverter can be uniquely identified for setting with NORD CON software or within a network.
P502
[-01]
...
[-03]
Value master function
(Master function value)
S
P
0 ... 57
{ all 0 }
Selection of master values of a Master for output to a bus system (see P503). These master
values are assigned at the slave via (P546):
[-01] =
Master value 1
[-02] =
Master value 2
[-03] =
Master value 3
Selection of possible setting values for master values:
00 =
Off
01 =
Actual frequency
02 =
Actual speed
03 =
Current
04 =
Torque current
05 =
Digital IO status
06 =
reserved
07 =
reserved
08 =
Setpoint frequency
09 =
Error number
10 =
reserved
11 =
reserved
12 =
BusIO Out Bits0-7
13 =
reserved
14 =
reserved
15 =
reserved
16 =
reserved
17 =
Value analogue input 1
18 =
Value analogue input 2
19 =
Setpoint frequency Master
value
20 =
Setpoint frequency after
master value ramp
21 =
Actual frequency without
master value slip
22 =
Speed encoder
23 =
Actual frequency with slip
24 =
Master value, actual
frequency with slip
53 =
Actual value 1 PLC
54 =
Actual value 2 PLC
55 =
Actual value 3 PLC
NOTE:
For details regarding the processing of setpoints and actual values, pleas refer to
Section 8.9 "Standardisation of setpoint / target values".
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...