2 Assembly and installation
BU 0180 en-4118
51
Analogue inputs
Actuation of device by external controller, potentiometer or the like.
Resolution
12Bit
U= 0 …10 V, R
i
=30 k
Ω
I= 0/4 … 20 mA
Burden resistance
(250
Ω
) via DIP switch
AIN1/2
Maximum permissible voltage at
analogue input: 30 V DC
Matching of the analogue signals is performed via P402 and
P403.
+ 10
V Reference voltage:
5 mA not short-circuit resistant
11
40
14
10
kΩ
11
10V REF
+ 10 V Reference voltage
-
-
14
AIN1+
Analogue input 1
P400 [-01]
Setpoint frequency
16
AIN2+
Analogue input 2
P400 [-02]
No function
40
GND
Reference potential GND
-
-
Digital inputs
Actuation of device using an external controller, switch or the like.
as per EN 61131-2 Type 1
Low: 0-
5 V (~ 9.5 kΩ)
High: 15-30 V (~ 2.5 -
3.5 kΩ)
Scan time:
1 ms
Reaction time:
≥
4 ms
Input capacitance:
10 nF
21
DIN1
Digital input 1
P420 [-01]
ON right
22
DIN2
Digital input 2
P420 [-02]
ON left
23
DIN3
Digital input 3
P420 [-03]
Fixed frequency 1 (
P465[-01])
Note:
Inputs DIN2 and DIN3 react more quickly than DIN 1
PTC resistor input
Monitoring of motor temperature using PTC
If the device is installed near the motor, a
shielded cable must be used.
The input is always active. In order to make the device
operational, a temperature sensor must be connected or both
contacts must be jumpered.
38
TF+
PTC resistor input
-
-
39
TF-
PTC resistor input
-
-
Control voltage source
Control voltage of device, e.g. for supplying accessories.
24 V DC ± 25 %, short circuit-proof
Maximum load 150 mA
1)
43
VO / 24V
Voltage output
-
-
40
GND / 0V
Reference potential GND
-
-
1)
See "Total currents" information (
Section 2.4.3 "Electrical connection of the control unit")
System bus
NORD-specific bus system for communicating with other devices (e.g. smart option
modules or frequency inverter)
Up to four frequency inverters (SK 2xxE,
SK 1x0E) can be operated on a single
system bus.
Address = 32 / 34 / 36 / 38
77
SYS H
System bus+
P509/510
Control terminals / Auto
78
SYS L
System bus-
P514/515
250kBaud / Address 32
dec
System bus terminating
resistance
Termination at the physical end of the bus system
If the device is supplied preassembled (e.g. equipped with customer unit SK CU4 / SK TU4) the terminating
resistors on the device and the module are factory-set. If other devices are going to be incorporated in the
system bus, the terminating resistors must be reset accordingly.
It must always be checked before
commissioning that the terminating resistors have been correctly set (1x at beginning and 1x at end
of system bus).
S1
Factory setting "OFF"
(For deviating factory setting, see
explanation above)
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...