4 Commissioning
BU 0180 en-4118
81
SK 1x0E
Connection of a KTY-84 to either of the two analogue inputs of the
SK 1x0E
is possible. In the
following examples, analogue input 2 of the frequency inverter is used.
SK 1x0E
*If necessary, also Terminal 40
Parameter settings
(Analogue input 2)
The following parameters must be set for the function of the KTY84-130.
1.
The motor data
P201-P207
must be set according to the rating plate.
2.
The motor stator resistance
P208
is determined at 20°C with
P220 = 1
.
3.
Function analogue input 2,
P400 [-02] = 30
(Motor temperature)
4.
The mode analogue input 2
P401 [-06] = 1
(negative temperatures are also measured)
5.
Adjustment of analogue input 2:
P402 [-06] = 1.54 V
and
P403 [-06] = 2.64 V
(with RV= 2.7
kΩ)
6.
Adjust time constants:
P404 [-02] = 400 ms
(Filter time constant is maximum)
7.
Motor temperature control (display):
P739 [-03]