5 Parameter
BU 0180 en-4118
157
P742
Data base version
(Database version)
S
0 ... 9999
Displays the internal database version of the FI.
P743
Inverter type
(Inverter type)
0.00 ... 250.00
Displays the inverter power in kW, e.g. "1.50"
⇒
FI with 1.5 kW nominal power.
P744
Configuration level
(Configuration level)
0000 ... FFFF
(hex)
This parameter displays the special devices integrated in the FI. Display is in hexadecimal code
(SimpleBox, Bus System).
The display is in plain text when the ParameterBox is used.
High byte:
Low byte:
00
hex
No extension
00
hex
Standard I/O
(SK 180E)
01
hex
reserved
01
hex
AS-i
(SK 190E)
02
hex
reserved
02
hex
--
P746
Module status
(Operating status of module)
SK 190E
0000 ... 0111
(bin)
or
00 ... 07 (hex)
Displays the current operating status of the AS interface.
Bit 0 =
AS interface voltage is present
Bit 1 =
AS interface watchdog set to active by master
Bit 2 =
AS interface connected
SimpleBox
: The binary bits are converted to a hexadecimal value and displayed.
ParameterBox:
The bits are displayed increasing from right to left (binary).
P747
Inverter Volt. Range
(Inverter
voltage range)
0 ... 2
Indicates the mains voltage range for which this device is specified.
0 =
100...120V
1 =
200...240V
2 =
380...480V
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...