4 Commissioning
BU 0180 en-4118
77
4.3.2.2 DIP switches (S1, S2)
The analogue inputs in the device are suitable for
current and voltage setpoints. For correct
processing of current setpoints (0-20
mA
/
4-20
mA
) the relevant DIP switch (
S1
– bit 2 or 3)
must be set to current signals ("
ON
").
DIP switch (
S1
– bit 1) sets the terminating
resistance of the system bus.
The system settings can be made via DIP switch
(
S2
). Settings made at DIP switch (S2) have
priority over the parameters P509, P514 and
P515.
As delivered, all DIP switches are in the "0" ("OFF") position.
No.
Bit
DIP switch (S1)
3
2
2
U/I A2
1)
Voltage / current
0 Analogue input 2 in voltage mode 0...10 V
1 Analogue input 2 in current mode 0/4...20 mA
2
2
1
U/I AI1
1)
Voltage / current
0 Analogue input 1 in voltage mode 0...10 V
1 Analogue input 1 in current mode 0/4...20 mA
1
2
0
T-SYS
Terminating resistance
0 System bus terminating resistance deactivated
I
System bus terminating resistance activated
1)
Adjustment to fail-safe signals in case of cable breaks (2-10 V / 4-20 mA) is made via parameters P402 and P403.
No.
Bit
DIP switch (S2)
3/2
2
2/1
SYS-ADR 0/1
System bus
Address/ baud rate
SYS-ADR
1
0
0
0
In accordance with P515 and P514 [32, 250kBaud]
0
I
Address 34, 250 kBaud
I
0
Address 36, 250 kBaud
I
I
Address 38, 250 kBaud
1
2
0
BUS-ON
Control word and
setpoint value source
0 In accordance with P509 and P510 [-01, -02]
I
System bus (
P509=3 and P510=3)
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...