NORDAC BASE (SK 180E / SK 190E) – Users Manual for Frequency Inverters
164
BU 0180 en-4118
E010
10.0
Bus Timeout
Telegram time-out / Bus off 24V int. CANbus
• Data transfer is faulty. Check P513.
• Check physical bus connections
• Check bus protocol program process.
• Check Bus Master.
• Check 24V supply of internal CAN/CANopen Bus.
• Node guarding error (internal CANopen)
•
Bus Off
error (internal CANbus)
10.2
Bus Timeout Option
Telegram timeout
• Telegram transfer is faulty.
• Check physical bus connections
• Check bus protocol program process.
• Check Bus Master.
• PLC is in the "STOP" or "ERROR" state.
10.4
Init error Option
Initialisation error in bus module
• Check Bus module current supply.
• DIP switch setting of a connected I/O extension
module is incorrect
10.1
System error option
System error bus module
• Further details can be found in the respective
additional bus instructions.
I/O extension:
• Incorrect measurement of the input voltage or
undefined provision of the output voltage due to error
in reference voltage generation.
• Short circuit at analogue output
10.3
10.5
10.6
10.7
10.9
Module missing / P120
The module entered in parameter (P120) is not available.
• Check connections
E011
11.0
Customer interface
Error in analog-digital converter
• Internal customer unit (internal data bus) faulty or
damaged by radio radiation (EMC)
• Check control connections for short-circuit.
• Minimize EMC interference by laying control and
power cables separately.
• Earth the devices and shields well.
E012
12.0
External watchdog
The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog
time<.
• Check connections
• Check setting P460
12.1
Limit moto./Customer
"Drive switch
-
off limit"
The drive switch-off limit (P534 [-01]) has triggered.
• Reduce load on motor
• Set higher value in (P534 [-01]).
12.2
Limit gen.
"Generator switch
-
off limit"
The generator switch-off limit (P534 [-02]) has triggered.
• Reduce load on motor
• Set higher value in (P534 [-02]).
12.3
Torque limit
Limit from potentiometer or setpoint source has switched off.
P400 = 12
12.4
Current limit
Limit from potentiometer or setpoint source has switched off.
P400 = 14
Summary of Contents for SK 180E Series
Page 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Page 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Page 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Page 211: ...Key word index BU 0180 en 4118 211...
Page 212: ...6071802 4118...