6 Assembly: Bell-type tank design
Maschinenfabrik Reinhausen GmbH 2015
90
4349315/00 EN
VACUTAP® VR®
Assembly: Bell-type tank design
WARNING
Risk of crushing from moving parts!
When the on-load tap-changer undertakes a tap-change operation, compo-
nents move on the selector and change-over selector, some of which are
freely accessible. Reaching into the selector or change-over selector during
a tap-change operation may result in serious injuries.
► Keep at a safe distance of at least 1 m during tap-change operations.
► Do not reach into the selector or change-over selector during tap-
change operations.
► Do not switch the on-load tap-changer when working on the selector
and change-over selector.
This chapter describes how to install the on-load tap-changer in a transform-
er in the bell-type tank design and how to dry it.
Preparatory work
Perform the work stated below before installing the on-load tap-changer in
the transformer.
Fitting mounting flange on transformer cover
A mounting flange is required for fitting the on-load tap-changer head on the
transformer cover. This can be supplied as an option or can be produced by
the customer. Mounting flanges made by the customer must comply with the
installation drawings in the appendix.
►
NOTICE!
Fit mounting flange on transformer cover (pressure tight).En-
sure that the sealing face makes complete contact and is not damaged.
Figure 94: Mounting flange
6
6.1
6.1.1
Summary of Contents for VACUTAP VR
Page 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Page 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Page 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Page 266: ......
Page 267: ......