6 Assembly: Bell-type tank design
Maschinenfabrik Reinhausen GmbH 2015
115
4349315/00 EN
VACUTAP® VR®
Removing on-load tap-changer head
Removing on-load tap-changer head cover
WARNING
Danger of death or severe injury!
Danger of death or severe injury from explosive gases under the on-load
tap-changer head cover!
► Ensure that there are no naked flames, hot surfaces or sparks (for ex-
ample caused by static charging) in the immediate surroundings and
that none occur.
► De-energize all auxiliary circuits (for example tap-change supervisory
control, pressure relief device, pressure-operated relays) before remov-
ing the on-load tap-changer head cover.
► Do not operate any electric devices during the work (for example risk of
sparks caused by impact wrench).
► Only use conductive and grounded hoses, pipes and pump equipment
that are approved for flammable liquids.
NOTICE
Damage to the on-load tap-changer and transformer!
Small parts in the oil compartment may block the diverter switch insert,
thereby damaging the on-load tap-changer and transformer!
► Take care to avoid parts falling into the oil compartment.
► Check that you have the same number of small parts when disassem-
bling and reassembling.
1.
Remove temporary fastening and spacers and slowly lower on-load tap-
changer.
Figure 129: Removing fastening
6.7
6.7.1
Summary of Contents for VACUTAP VR
Page 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Page 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Page 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Page 266: ......
Page 267: ......