10 Transporting transformer to the operating site
Maschinenfabrik Reinhausen GmbH 2015
216
4349315/00 EN
VACUTAP® VR®
Emptying oil compartment via pipe connection S
WARNING
Danger of death or severe injury!
Danger of death or severe injury from explosive gases under the on-load
tap-changer head cover!
► Ensure that there are no naked flames, hot surfaces or sparks (for ex-
ample caused by static charging) in the immediate surroundings and
that none occur.
► De-energize all auxiliary circuits (for example tap-change supervisory
control, pressure relief device, pressure-operated relays) before remov-
ing the on-load tap-changer head cover.
► Do not operate any electric devices during the work (for example risk of
sparks caused by impact wrench).
► Only use conductive and grounded hoses, pipes and pump equipment
that are approved for flammable liquids.
1.
De-energize all auxiliary circuits (for example the tap-change superviso-
ry control, pressure relief device, pressure monitoring device).
2.
If the stop-cock (slide valve) between the oil conservator and oil com-
partment is open, open the air-vent valve E1 on the on-load tap-changer
head.
3.
Drain off the gas from under the on-load tap-changer cover. Ensure suf-
ficient fresh air (for example in transformer cells and work tents).
4.
Once the gas has been drained off and the oil is flowing out of the air-
vent valve, close this valve and close the stop-cock between the oil con-
servator and oil compartment.
5.
Open air-vent valve again and drain off around 5–10 liters of oil via the
pipe connection S until the area under the on-load tap-changer head
cover is free of oil.
6.
Loosen 24 screws M10/wrench size 17 with safety elements on on-load
tap-changer head cover.
7.
Remove the on-load tap-changer head cover.
8.
Extract oil via pipe connection S.
9.
Open stop-cock between oil conservator and oil compartment.
ð
The oil from the oil conservator flows into the oil compartment.
10. Extract oil via pipe connection S.
11. Place the on-load tap-changer head cover on the on-load tap-changer
head.
12. Use 24 screws M10/wrench 17 and safety elements to screw down on-
load tap-changer head cover (tightening torque 34 Nm).
10.3.1
Summary of Contents for VACUTAP VR
Page 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Page 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Page 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Page 266: ......
Page 267: ......