8 Fitting protective devices and drive components
Maschinenfabrik Reinhausen GmbH 2015
206
4349315/00 EN
VACUTAP® VR®
Figure 278: Tightening lower coupling brackets
18. Fit upper coupling brackets with 3 mm axial clearance.
Figure 279: Fitting upper coupling brackets
19. Working from top to bottom, mount the individual parts of the shaft pro-
tection. Set angle position between both parts of pivotable protective
tube and fix with available hose clip. Secure both upper and lower pro-
tective tubes with a hose clip at both ends. Secure the two telescopic
protective tubes to one another using a hose clip.