6 Assembly: Bell-type tank design
Maschinenfabrik Reinhausen GmbH 2015
111
4349315/00 EN
VACUTAP® VR®
To actuate the drive shaft of the upper gear unit of the on-load tap-changer
head, you can use a short tube (diameter 25 mm) with screwed-in coupling
bolt (diameter 12 mm) with a hand wheel or crank.
Figure 126: Upper gear unit with hand crank
If using more than one on-load tap-changer column with a shared drive, you
have to link all on-load tap-changer heads to one another by the horizontal
drive shaft part.
1.
NOTICE!
Only move on-load tap-changer into the desired operating po-
sition (8.25 revolutions) via drive shaft of the upper gear unit. When us-
ing a drill, do not exceed a maximum speed of 250 rpm. The diverter
switch operation can be heard distinctly.
2.
NOTICE!
After operating the diverter switch, continue to crank 2.5 revo-
lutions in the same direction on the drive shaft of the upper gear unit in
order to correctly end the tap change operation. An incomplete tap-
change operation may damage the on-load tap-changer!
When actuating the change-over selector a higher torque is required.