8 Fitting protective devices and drive components
Maschinenfabrik Reinhausen GmbH 2015
165
4349315/00 EN
VACUTAP® VR®
4.
Close terminal box.
Figure 218: Terminal box cover
The associated contact positions for checking electrical continuity are evi-
dent from the dimensional drawing provided.
Installing protective relay in piping
The following requirements must be satisfied in order to install the protective
relay in the piping:
▪
The pipes from the protective relay to the oil conservator must be routed
with an inclination of at least 2 % to ensure the switching gases can es-
cape freely.
▪
The inner piping diameter must be at least 25 mm.
▪
The magnetic field strength (bushings, busbars etc.) must be < 20 kA/m.
▪
Install protective relay with good support and free from vibrations.
▪
The test buttons must be at the top.
8.2.2