6 Assembly: Bell-type tank design
Maschinenfabrik Reinhausen GmbH 2015
101
4349315/00 EN
VACUTAP® VR®
3.
Temporarily fasten on-load tap-changer to supporting structure. The
supporting flange has through holes for this purpose.
Figure 112: Fastening the on-load tap-changer
Connecting tap winding and on-load tap-changer take-off
lead
NOTICE
Damage to the on-load tap-changer!
Connecting leads which place mechanical strain on the on-load tap-changer
will damage the on-load tap-changer!
► Produce connections with care.
► Do not twist connection contacts.
► Connect connecting leads without warping or deforming.
► If necessary use an expansion loop for connecting leads.
► Fit screening caps provided to screw connections.
The tap winding and on-load tap-changer take-off lead must be connected in
accordance with the connection diagram included with the delivery.
Tap selector connection contacts VRC/VRE
The selector connection contacts are indicated on the selector bars, have
crimped ends and a through-hole for M10 screws to allow the selector take-
off leads to be connected by means of cable shoes.
The screening caps are supplied separately.
In this case a locking washer must be placed below each screening cap. The
M10 connection screws, the nuts, and locking washers are not included in
the scope of delivery.
6.3
6.3.1
Summary of Contents for VACUTAP VR
Page 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Page 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Page 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Page 266: ......
Page 267: ......