12 Fault elimination
Maschinenfabrik Reinhausen GmbH 2015
223
4349315/00 EN
VACUTAP® VR®
Fault elimination
WARNING
Danger of death or severe injury!
Danger of death or severe injury from explosive gases under the on-load
tap-changer head cover!
► Ensure that there are no naked flames, hot surfaces or sparks (for ex-
ample caused by static charging) in the immediate surroundings and
that none occur.
► De-energize all auxiliary circuits (for example tap-change supervisory
control, pressure relief device, pressure-operated relays) before remov-
ing the on-load tap-changer head cover.
► Do not operate any electric devices during the work (for example risk of
sparks caused by impact wrench).
► Only use conductive and grounded hoses, pipes and pump equipment
that are approved for flammable liquids.
NOTICE
Damage to the on-load tap-changer and transformer!
Tripping of the protective relay or other protective devices can indicate dam-
age on the on-load tap-changer and transformer! The transformer must not
be energized without first undertaking checks!
► Check on-load tap-changer and transformer when protective relay or
other protective devices have been tripped.
► Do not use the equipment again until you are sure there is no damage
to the on-load tap-changer or transformer.
The table below is intended to assist with detecting and, where possible,
remedying faults.
For more information, please consult the operating instructions for the RS
protective relay or the relevant protective device.
In the event of faults on the on-load tap-changer and motor-drive unit, which
cannot be easily corrected on site, or if the RS protective relay or additional
protective devices have been tripped, please inform your authorized MR rep-
resentative, the transformer manufacturer or contact us directly at:
Maschinenfabrik Reinhausen GmbH
Technischer Service
Postfach 12 03 60
93025 Regensburg
Germany
Phone: +49 94140 90-0
Fax: +49 9 41 40 90-7001
E-mail: [email protected]
Internet: www.reinhausen.com
Error pattern
Action
Tripping of protective relay (for example RS)
12
Summary of Contents for VACUTAP VR
Page 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Page 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Page 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Page 266: ......
Page 267: ......