12 Fault elimination
Maschinenfabrik Reinhausen GmbH 2015
225
4349315/00 EN
VACUTAP® VR®
Error pattern
Action
Deviation from desired value during transformer ratio
test
Contact manufacturer of transformer and, if necessa-
ry, MR and provide measured values.
Deviation from limit value for diverter switch oil val-
ues
Carry out oil change, check oil conservator breather
of on-load tap-changer.
Table 10: Fault elimination
Tripping of the protective relay and re-commissioning the
transformer
WARNING
Danger of death or severe injury!
Danger of death or severe injury if on-load tap-changer and transformer are
insufficiently tested!
► Be sure to check on-load tap-changer and transformer after the protec-
tive relay has been tripped. The diverter switch insert or selector switch
insert must be removed in order to do this.
► Only use the equipment again when you are sure there is no damage to
the on-load tap-changer or transformer.
When the circuit breakers have been tripped by the protective relay, proceed
as follows:
1.
Establish time of tripping.
2.
Determine operating position of on-load tap-changer.
3.
As a precaution, block the motor-drive unit by tripping the motor protec-
tive switch to prevent the on-load tap-changer being actuated by remote
control.
4.
Check on-load tap-changer head cover. If oil is leaking, shut the oil con-
servator stop valve immediately.
5.
Check whether the flap valve of the protective relay is in the OFF or IN
SERVICE position.
Flap valve in IN SERVICE position
If the flap valve is in the IN SERVICE position, there may be a fault in the
tripping circuit. Check the tripping circuit. If the reason for the protective relay
tripping cannot be found, the diverter switch insert or selector switch insert
must be removed in accordance with the on-load tap-changer's operating in-
structions and checked [
Flap valve in OFF position
Note that protective relay RS 2004 features an automatic reset mechanism
which means that the flap valve does not remain in the OFF position after
tripping. If the protective relay RS 2004 has not tripped due to an error in
the tripping circuit, proceed as described below for RS 2004 too.
12.1
12.1.1
12.1.2
Summary of Contents for VACUTAP VR
Page 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Page 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Page 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Page 266: ......
Page 267: ......