13 Technical data
Maschinenfabrik Reinhausen GmbH 2015
228
4349315/00 EN
VACUTAP® VR®
Technical data
An overview of all key technical data for the on-load tap-changer and motor-
drive unit exists in the form of separate documents, which are available on
request.
Technical data for protective relay
General technical data
Housing
Outdoor model
Degree of protection
Relay actuation
Flap valve with aperture
Weight
About 3.5 kg
Oil flow speed of available types
when tripping (oil temperature 20 °C)
0.65 m/s
1.20 m/s
3.00 m/s
4.80 m/s
Table 11: General technical data
Tripping circuit
The protective relay can be supplied with either a normally open (NO) or a
normally closed (NC) dry-reed magnetic switch (see dimensional drawing
supplied).
Other contact combinations are available as special design [
Electrical data for normally open (NO) or normally closed (NC) dry-reed
magnetic switch
AC switching capacity
DC switching capacity
1.2 VA…400 VA
1.2 W…250 W
Maximum admissible voltage AC/DC
Minimum admissible voltage AC/DC
250 V
24 V
Maximum switched current AC/DC
Minimum switched current AC/DC
2 A
4.8 mA at 250 V