2 Safety
Maschinenfabrik Reinhausen GmbH 2015
16
4349315/00 EN
VACUTAP® VR®
DANGER
Danger of death or severe injury and damage to property and
the environment!
Danger of death or severe injury and damage to property and the environ-
ment due to electrical voltage, falling and/or tipping parts as well as danger-
ous cramped conditions resulting from moving parts!
► Adherence to the following prerequisites and conditions is mandatory.
► Adhere to warning notices.
Since the on-load tap-changer was dimensioned as per IEC 60214-1, it can
switch currents of up to twice the value of the rated through current.
On-load tap-change operations are not to be performed during operating
conditions with higher currents.
Examples of such operating conditions are:
▪
Inrush current impulses when transformers are switched on
▪
Short circuit
The rated step voltage may be briefly exceeded by up to 10 % as long as the
rated through current is not exceeded. Such an operating condition can oc-
cur due to overexcitation of the transformer after load shedding, for example.
The on-load tap-changer can be operated in the temperature range of the
surrounding transformer oil of between -25 ° and +105 °C and with overload
up to +115 °C in accordance with IEC 60214-1.
Inappropriate use
Use is considered to be inappropriate if the product is used other than as de-
scribed in the Appropriate use [
15] section. Please also note the following:
▪
Risk of explosion and fire from highly flammable or explosive gases, va-
pors, or dusts. Do not operate product in areas at risk of explosion.
▪
Unauthorized or inappropriate changes to the product may lead to per-
sonal injury, material damage, and operational faults. Only modify prod-
uct following discussion with Maschinenfabrik Reinhausen GmbH.
Personnel qualification
The product is designed solely for use in electrical energy systems and facili-
ties operated by appropriately trained staff. This staff comprises people who
are familiar with the installation, assembly, commissioning and operation of
such products.
2.3
2.4
Summary of Contents for VACUTAP VR
Page 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Page 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Page 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Page 266: ......
Page 267: ......