8 Fitting protective devices and drive components
Maschinenfabrik Reinhausen GmbH 2015
176
4349315/00 EN
VACUTAP® VR®
Figure 234: OPERATION position
1 Snap-action switch
2 Sensor in the OPERATION position
4.
Secure the cover cap.
Always check the position of the sensor!
Installing the pressure-operated relay
The pressure-operated relay can be installed in 2 variants.
▪
Fastening on the on-load tap-changer head (vertical installation)
▪
Fastening onto a pipe bend (horizontal installation)
It is installed using holes on the mounting ring. A mounting seal has to be
installed under the pressure-operated relay during installation.
During fastening, ensure that the ventilation is on top.
Ensure that there is sufficient space above the pressure-operated relay to
remove the cover cap.
8.3.2