5 Assembly: Standard design
Maschinenfabrik Reinhausen GmbH 2015
87
4349315/00 EN
VACUTAP® VR®
2.
Insert position-indication disk horizontally between panel and bracket
and fit cover disk. Align tap position indicator disc and cover disk to pro-
duce a continuous red line.
Figure 89: Inserting position-indication disk
3.
Secure cover disk with countersunk head screw. The countersunk head
screw must be suitable for center-punching.
Figure 90: Fastening cover disk
4.
Secure countersunk head screw by center-punching.
Securing on-load tap-changer head cover
1.
NOTICE!
Place the on-load tap-changer head cover on the on-load tap-
changer head and take care not to damage the o-ring inserted in the on-
load tap-changer head cover. A damaged o-ring will cause oil to escape
5.7.2.3.6