8 Fitting protective devices and drive components
Maschinenfabrik Reinhausen GmbH 2015
181
4349315/00 EN
VACUTAP® VR®
NOTICE
Damage to the on-load tap-changer!
Damage to the on-load tap-changer by actuating the on-load tap-changer
without oil!
► Before actuating the on-load tap-changer for the first time, the tap se-
lector must be completely immersed in transformer oil and the oil com-
partment completely filled with oil.
► The on-load tap-changer can be operated in the temperature range of
the surrounding transformer oil of between -25 ° and +105 °C and with
overload up to +115 °C in accordance with IEC 60214-1.
Observe the following during mounting:
NOTICE
Damage to drive and on-load tap-changer or off-circuit tap-
changer!
Trouble-free operation of the motor-drive and the on-load tap-changer or
off-circuit tap-changer cannot be guaranteed.
► The shaft ends to be connected must be exactly aligned.
Minor axial displacement can be tolerated as long as it does not exceed
35 mm per 1000 mm square tube length (that corresponds to 2°).
Square tubes, coupling brackets, coupling bolts, screws, and locking wash-
ers are corrosion-resistant. We therefore recommend not applying the same
external coating to these parts as to the transformer tank.
The square tubes and the vertical protective cover are supplied in over-
lengths (graded standard lengths). These parts must be cut to the required
size before mounting on the transformer. In rare cases the inner tube of the
telescopic protective tube has to be cut.
Standard lengths
Motor-drive unit
Manual drive
400
•
•
600
•
•
900
•
•
1300
•
•
1700
•
•
2000
•
•
2500
Not permitted
•
1)
Table 9: Graded standard lengths of square tubes
The maximum total drive shaft length of the drive - last pole = 15 m.
1)
I>2000 only possible for vertical installation without shaft protection! Tele-
scopic protective tubes for manual drives with vertical dimensions V1> 2462
should be delivered vertically, similar to the motor-drive unit with intermedi-
ate bearing.
Summary of Contents for VACUTAP VR
Page 1: ...On Load Tap Changer VACUTAP VR Installation and Commissioning Instructions 4349315 00 EN ...
Page 246: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 246 4349315 00 EN VACUTAP VR ...
Page 248: ...14 Appendix Maschinenfabrik Reinhausen GmbH 2015 248 4349315 00 EN VACUTAP VR ...
Page 266: ......
Page 267: ......