13 Technical data
Maschinenfabrik Reinhausen GmbH 2015
230
4349315/00 EN
VACUTAP® VR®
Technical data for pressure monitoring device
General technical data
Setup
Outdoor model
Ambient temperature
-40 °C…+80 °C (mechanical)
Cable connection
M25x1.5
Degree of protection
IP 55 in accordance with IEC 60529 (enclosed
device)
Relay actuation
Corrugated tubing with counter-pressure spring
Oil temperature
-40 °C – +100 °C
Weight
About 1.2 kg
Equipment
For standard insulating fluids (IEC60296 and
IEC60422) and alternative insulating fluids
Sealing material
(oil – air)
VITON
Permitted pressure range
(absolute pressure)
1 bar…6 bar, vacuum not permitted
Upper switching pressure 3.8 ±0.2 bar (trip pressure)
Lower switching pressure 2.8 ± 0.2 bar
Snap-action switch
Connection terminals
Line connection: 1 or 2 lines per terminal
(Ø 0.75…2.5 mm²)
Contacts
1xNO (normally open), 1xNC (normally closed)
Utilization category
IEC 60947-5-1:
AC 15: 230 V/1 A
DC 13: 60 V/0.5 A
Maximum continuous cur-
rent
10 A
Rated insulation voltage
AC: 2.5 kV/min
Table 14: General technical data