Troubleshooting
5-62 Manual # 42-02-2P24
ICE-COP-2 Car Panel Interface Board
The ICE-COP-2 board, mounted in the car operating panel, converts the discrete closures from
the panel buttons and switches to data on the CAN serial bus and passes it through the MC-LSI
Landing System Interface board on the cartop, up the traveler to the car controller. Additional
ICE-COP-2 boards are used to accommodate rear doors or installations with many floors, COP
buttons, and lamps.
Spare assignable inputs to and outputs from ICE-COP-2 boards are available depending upon
system configuration.
• F1 menu, Serial COP Board Type = ICE-COP-2: ICE-COP-2 board assignable inputs show
up in the Spare Inputs menu as COP FX (front panel board) IO1 - IO7; COP Rx (rear panel
board) IO1 - IO7. Spare outputs (Spare Outputs menu) appear as IO-13 - IO-19 (COP FX
and COP RX).
If the job has ICE-COP-2 boards, unused spare inputs to and outputs from these boards must be
set to NOT USED. If controller software is upgraded in the field, it is very important to check
programmable ICE-COP-2 board inputs and outputs and verify unused connections are set to
NOT USED.
Please refer to “Spare Inputs Menu Options” on page 4-27.
Caution
Spare inputs and outputs used on the
ICE-COP-2
boards must be 24VDC, not to exceed 6 Watts.
Installation Instructions
1. Turn the power off at the main disconnect.
2. Mount the ICE-COP-2 board(s) inside the COP using the supplied hardware and provid-
ing sufficient clearance for the components.
Caution
Do not replace C-RJ11-CAN-15 cables between the
ICE-COP-2
and MC-LSI with RJ11 cables pur-
chased locally. These cables MUST be replaced with C-RJ11-CAN-15 supplied by MCE. For a replace-
ment cable, please contact MCE technical support.
3. Refer to the prints for the job to wire the ICE-COP-2 board.
Caution
This system is designed for 24 VDC circuits only!
Do not connect 120 VAC or DC to any
terminal on the ICE-COP-2 board.
Connect only the 24V power from connector J34
(24V CUSTOMER LOAD SUPPLY) to the load.
Summary of Contents for Motion 4000
Page 20: ...xiv Manual 42 02 2P24 5 20 13 ...
Page 38: ...Motion 4000 Traction Elevator Control 1 18 Manual 42 02 2P24 ...
Page 178: ...Final Adjustments 3 56 Manual 42 02 2P24 ...
Page 322: ...User Interface 4 144 Manual 42 02 2P24 ...
Page 391: ...PC Board Quick References 5 69 5 Motion 4000 Figure 5 11 Example MC CPI Wiring ...
Page 439: ...Customer Notations A 27 A Motion 4000 Customer Notations Table A 4 Customer Notation Area ...
Page 444: ...Appendix A 32 Manual 42 02 2P24 ...