Final Adjustments
3-54 Manual # 42-02-2P24
Check the MCE drawings to verify that the car is properly connected to the emergency generator
and that emergency power (F1, Extra Features Menu) is set up appropriately. A typical genera-
tor connection is shown below.
Figure 3.4 Typical Emergency Generator Connection
1. Disconnect power from the controller.
2. When the emergency generator comes on line, the EPI input to the controller should be
activated.
3. The car will recall to the assigned floor.
4. If the EPRUN input (not shown) is activated, the designated car will respond to hall and
car calls. Otherwise, the car will remain at the recall floor.
5. Restore normal power to the controller. If running, the designated car will stop, wait
until normal power is fully established, then resume normal operation.