F7: Parameters Adjust
4-135
4
Motion 4000
Contract Overspeed, 145
The setting in feet per minute above contract speed at
which a contract overspeed is detected and an emergency stop initiated. Generally set to about
8% above contract speed with variance due to the tracking accuracy of the drive/motor.
• 8% x contract speed + contract speed = overspeed
• Example for 350 FPM: 8% of 350 = 28 + 350 = 378 FPM
Inspection Overspeed, 146
The setting in feet per minute above inspection speed at
which an inspection overspeed is detected and an emergency stop initiated. Generally set to
about 8% above inspection speed with variance due to the tracking accuracy of the drive/motor.
• 8% x inspection speed + inspection speed = overspeed
• Example for 50 FPM: 8% of 50 = 4 + 50 = 54 FPM
Leveling Overspeed, 147
The setting in feet per minute above leveling speed at
which a leveling overspeed is detected and an emergency stop initiated. Generally set to about
8% above leveling speed with variance due to the tracking accuracy of the drive/motor.
• 8% x leveling speed + leveling speed = overspeed
• Example for 20 FPM: 8% of 20 = 1.6 + 20 = 21.6 FPM
Hoist Motor Speed, 148
Enter the motor RPM at which the car achieves contract
speed (KEB LF.11). This information is available from the motor nameplate and is visible on
KEB RU.7 when the car is running at contract speed. This rated motor RPM is the synchronous
motor RPM minus slip RPM.
• Example for 6-pole geared machine: 1200 RPM (synchronous), 1165 RPM (rated).
Contract Speed, 149
Enter the contract speed of the car in feet per minute.
High Speed, 150
Enter the high speed limit for the Standard curve. Normally set to the
same as Contract Speed. (Can be used to change car speed without changing profile.)
Intermediate Speed, 151
Enter the reduced speed at which the car is to run when
the SPI1 (Spare 1) input to the TC-MPI board is active. Intermediate speed uses the standard
curve.
Earthquake Speed, 152
If the elevator is allowed to run after a seismic event, this is
the speed that will be used. Default is 150 FPM.
Auxiliary Speed, 153
If the group control commands the car to run at economy speed,
this is the speed that will be used. The group may command cars to run at normal contract
speed during busy traffic or in response to a timer setting, or at reduced economy speed during
light traffic or in response to a timer setting. Selected when the SPI2 (Spare 2) input to the TC-
MPI board is active.
Backup Power Speed, 154
If commercial power is lost and the elevator has genera-
tor backup power available, this is the speed that will be used.
Inspection Speed (Normal), 155
Enter the normal Inspection Speed for the car.
Summary of Contents for Motion 4000
Page 20: ...xiv Manual 42 02 2P24 5 20 13 ...
Page 38: ...Motion 4000 Traction Elevator Control 1 18 Manual 42 02 2P24 ...
Page 178: ...Final Adjustments 3 56 Manual 42 02 2P24 ...
Page 322: ...User Interface 4 144 Manual 42 02 2P24 ...
Page 391: ...PC Board Quick References 5 69 5 Motion 4000 Figure 5 11 Example MC CPI Wiring ...
Page 439: ...Customer Notations A 27 A Motion 4000 Customer Notations Table A 4 Customer Notation Area ...
Page 444: ...Appendix A 32 Manual 42 02 2P24 ...