14 TROUBLESHOOTING
Event ID
0 to FFFF
H
Error content
Corrective action
279 (117
H
)
An error occurred when writing to registry database.
• After installing SW0DNC-MNETH-B, restart the
computer and confirm that this error does not
occur.
• Increase the system memory and disk capacity.
• When the error has occurred at updating
Windows
R
8.1 or upgrading the operating
system with the software package installed,
reinstall the software package.
280 (118
H
)
A request that cannot be processed was received from other
station.
——
281 (119
H
)
Retry transmission was executed during transmission
process.
——
286 (11E
H
)
Failed to allocate the Memory Area.
Increase the memory.
287 (11F
H
)
Link Parameter is nothing or has abnormal data.
Set the parameter with MELSECNET/H utility,
and reset the board.
288 (120
H
)
The Driver WDT error occurred on the MELSECNET/H board
driver side.
Remove another option board.
Take corrective actions for the Driver WDT error.
(Refer to Section 14.7.2.)
295 (127
H
)
The Board WDT error had occurred.
Replace the MELSECNET/H board.
296 (128
H
)
The CLOCK STOP error had occurred.
297 (129
H
)
The Target Abort error had occurred on the PCI bus.
304 (130
H
)
The Data Parity error had occurred on the PCI bus.
305 (131
H
)
Entering sleep mode or hibernation mode, or fast startup is
detected.
The board is not operated normally because the sleep mode,
hibernation mode, and fast startup is not supported by the
board.
Change the power option not to enter the sleep
mode, hibernation mode, or disable the fast
startup function and restart the personal
computer.
33027 (8103
H
)
The driver is not yet started, or an error occurred while
opening the driver.
Correct the cause of the driver error, then restart
the PC.
33029 (8105
H
)
An error occurred while resetting the MELSECNET/H board.
One of the following two conditions is suspected as the cause.
1) The common memory area used by the MELSECNET/H
board may be in contention with other device.
2) No response was received from the MELSECNET/H
board.
1) Check for overlapping setting with other
optional board.
2) Perform memory and I/O diagnosis using the
MNETH utility. If the error persists, replace the
MELSECNET/H board.
1 : If an event error occurs in event viewer, make the following setup setting on the PC.
(Limited to the PC includes those setup setting items.)
Example)
BIOS Setup Utility
Plug & Play O/S
: [YES] [No]
Reset Configuration Data : [No] [YES]
Then, restart the PC.
Summary of Contents for Q80BD-J71BR11
Page 2: ......
Page 24: ...A 22 A 22 MEMO ...
Page 50: ...4 6 4 6 MELSEC 4 FUNCTION MEMO ...
Page 92: ...6 36 6 36 MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION MEMO ...
Page 132: ...10 2 10 2 MELSEC 10 MELSEC DATA LINK LIBRARY MEMO 10 ...
Page 138: ...11 6 11 6 MELSEC 11 PROGRAMMING MEMO ...
Page 164: ...12 26 12 26 MELSEC 12 APPLICATION FUNCTIONS MEMO ...
Page 166: ...13 2 13 2 MELSEC 13 ERROR CODE MEMO 13 ...
Page 223: ......