(3) Precautions on external power supply cable wiring
CAUTION
•
Verify the rated voltage and pin assignment of the product and connect the external
power supply cable properly.
Connecting a power supply with a different voltage rating, imperfect cable crimping
or faulty wiring may cause a fire or failure.
•
Use a specified tool for crimping of the cable and contacting pin. Imperfect crimping
may cause malfunction.
•
Verify the pin assignment and fully insert the crimped contacting pin into the
connector. Imperfect insertion may cause failure or malfunction.
•
Insert the wired external power supply cable into the external power supply cable
connector until a click is heard. Imperfect insertion may cause failure or
malfunction.
•
Keep the external power supply cable away from the main circuit cable, power
cables and/or load cables connected to other than programmable controllers.
Ensure a distance of 100mm between them. Failure to do so may result in
malfunction due to noise, surge or induction.