7 PARAMETER SETTINGS
(2) Screen settings (Common parameter setting screen)
Perform the setting of each station's transmission range (LB/LW settings) in the
"Common parameter setting" screen in the MNETH utility.
POINT
In order to validate the guarantee of 32-bit data, it is necessary that the number of
points in each station's transmission range be a multiple of 20
H
for LB and a
multiple of 2 for LW and that each station's top device No. be set so that the LB is a
multiple of 20
H
and the LW is a multiple of 2. (For details on guaranteeing 32-bit
data, refer to the "Q Corresponding MELSECNET/H Network System Reference
Manual (PLC to PLC Network)".)