12 APPLICATION FUNCTIONS
(3) System timer interval
The low-speed cyclic data are sent in the link cycle at the designated time.
By omitting year, month, and day in the setting, the low-speed cycle transmission
can be activated yearly (or monthly, or daily). Hour, minute and second values
must be entered.
Setting points: 1 to 8 points
[Setting method]
1) Click ( )"System times" to select.
2) Set year, month, day, hour, minute and second to the designated time.
In the following screen example:
Points 1 to 3
: By omitting year, month and day, data is sent every
day at the designated time.
Points 4 and 5 : By omitting year and month, data is sent at the
designated time monthly.
Point 6
: By omitting the year, data is sent at the designated
time every year.
Points 7 and 8 : Data is sent only once at the designated time.
POINT
(1) The system timer operates based on the host's clock.
If used without matching the clocks on the sending station and receiving
station, there may be a time gap between the stations.
(2) When handling multiple data without the block guarantee per station function,
new and old data may coexist.
Apply interlocks to prevent the coexistense.
Summary of Contents for Q80BD-J71BR11
Page 2: ......
Page 24: ...A 22 A 22 MEMO ...
Page 50: ...4 6 4 6 MELSEC 4 FUNCTION MEMO ...
Page 92: ...6 36 6 36 MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION MEMO ...
Page 132: ...10 2 10 2 MELSEC 10 MELSEC DATA LINK LIBRARY MEMO 10 ...
Page 138: ...11 6 11 6 MELSEC 11 PROGRAMMING MEMO ...
Page 164: ...12 26 12 26 MELSEC 12 APPLICATION FUNCTIONS MEMO ...
Page 166: ...13 2 13 2 MELSEC 13 ERROR CODE MEMO 13 ...
Page 223: ......