3 - 3 3 - 3
MELSEC
3 SPECIFICATIONS
1: The CPU usage may be higher compared to that of Q80BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BDJ71LP21G,
Q80BD-J71LP21GE, or Q80BD-J71BR11. (For the solutions to slow PC performance, refer to Section 14.8.)
2: MELSECNET/H board communications rate and Mode settings are performed using the MNETH Utility.
(For details, refer to Section 9.2.3)
3: L type and H type of the previous optical fiber cable (A-2-
) differ in the distances between stations. (For details, refer
to Section 6.4.1)
(2) Q80BD-J71BR11
Specifications
Item
Q80BD-J71BR11
LX/LY 8192
Points
LB
16384 Points (When in the MELSECNET/10 Mode
1
: 8192 Points)
Maximum links
in 1 network
LW
16384 Points (When in the MELSECNET/10 Mode
1
: 8192 Points)
Maximum links in 1 station
• MELSECNET/H mode, MELSECNET/10 mode
1
{(LY + LB) / 8 + (2 LW)}
≤
2000 bytes
• MELSECNET/H Extended mode
1
{(LY + LB) / 8 + (2 LW)}
≤
35840 bytes
Communications rate
1
10
Mbps
Number of stations Connected
to 1 network
32 Stations (Control station: 1; normal station: 31)
Connection cable
Optical fiber cable
Coaxial cable
Total extension cable length in
1 network
Cable name
3C-2V
5C-2V
300 m
2
500 m
2
Total extension
cable length
Length between
stations
5C-FB
Can be extended to 2.5 km (8202.5 ft.) using a repeater unit (A6BR10, A6BR10-DC).
Maximum networks
239
Maximum number of groups
32 (When in the MELSECNET/10 Mode: 9)
Transmission channel format
Single Bus
Communications system
Token bus system
Synchronization system
Frame synchronization system
Encoding system
NRZI encoding (Non return to Zero inverted)
Manchester encoding
Transfer format
HDLC Standard (Frame format)
Error control system
CRC (X16 + X12 + X5 + 1) and retry by overtime.
RAS function
• Loop back function (optical loop system only) by abnormal detection and cable disconnection.
• System down prevention through control station.
• Error detection by the link special relay and link special register.
etc.
Transient transmission
N:N communications
Special cyclic transmission
Low speed cyclic transmission
Number of boards that can be
installed
Maximum 4 boards
Installation slot
PC PCI bus slot (half size)
Exclusive slots
1 slot
5 V DC Internal current
consumption
0.67 A
Weight 0.11
kg
1: MELSECNET/H board communications rate and Mode settings are performed using the MNETH Utility.
(For details, refer to Section 9.2.3)
2: Depending on the number of stations connected, there are limits to the cable length between stations. (For details, refer
to Section 6.4.2)
Summary of Contents for Q80BD-J71BR11
Page 2: ......
Page 24: ...A 22 A 22 MEMO ...
Page 50: ...4 6 4 6 MELSEC 4 FUNCTION MEMO ...
Page 92: ...6 36 6 36 MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION MEMO ...
Page 132: ...10 2 10 2 MELSEC 10 MELSEC DATA LINK LIBRARY MEMO 10 ...
Page 138: ...11 6 11 6 MELSEC 11 PROGRAMMING MEMO ...
Page 164: ...12 26 12 26 MELSEC 12 APPLICATION FUNCTIONS MEMO ...
Page 166: ...13 2 13 2 MELSEC 13 ERROR CODE MEMO 13 ...
Page 223: ......